Procedure for setting up communication – Yaskawa iQpump Controller User Manual User Manual

Page 215

Advertising
background image

D.1 Using Modbus Communication

YASKAWA

TM.iQp.06 iQpump Controller User Manual

215

Figure D.2 Communication Connection Terminals and Terminating Resistance

IMPORTANT:

1. Separate the communication cables from the main circuit cables and control circuit wiring.
2. Use shielded cables for the communication cable, and use proper shield clamps.

3. When using RS-485 communication, connect S+ to R+, and S- to R-, on the control circuit terminal board. See

Figure D.3

below.

4. Shield at one end only.

Figure D.3 RS-485 Communication Connection

Procedure for Setting Up Communication

Use the following procedure to perform communication with the DDC.

1. Turn OFF the input to the iQpump drive power and connect the communication cable between the PLC and the iQpump drive.

2. Turn ON the input power to the iQpump drive.
3. Set the required communication parameters (H5-01 to H5-09) using the digital operator.
4. Turn OFF the input to the iQpump drive power, and check that the digital operator display has disappeared.

5. Turn ON the input power to the iQpump drive once again.
6. Perform communication with the DDC.

Terminating resistance (1/2W, 110 Ohms)

RS-422A
or RS-485

Switch

S1

O
F
F

1

Terminating
resistance

DIP Switch S1-1 located on
terminal board.

2

1

Advertising