Application examples, Simple duplex system, G.9 iqpump software multiplexing set-up – Yaskawa iQpump Controller User Manual User Manual

Page 258: Figure g.15 simplified wiring diagram

Advertising
background image

258

YASKAWA

TM.iQp.06 iQpump Controller User Manual

G.9 iQpump Software Multiplexing Set-up

Application Examples

Simple Duplex System

A customer requires a duplex system with the following capabilities:

Control the system pressure using 2 iQpump drives (no PLCs).

• Alternate iQpump drives everyday to even out the pump wear.
• Toggle switch for Run command.

Each iQpump drive will have its own feedback transducer and because of shut-off valves, the network feedback as a back-up should not be used.

Pump is at optimal running speed when running at fixed speed is 54.0 Hz.

Setpoint is 100 psi, feedback scale is 145 psi, start level is 80 psi.

Figure G.13

Figure G.15 Simplified Wiring Diagram

Related Parameters for Simple Duplex System Example

P9-29



089C

Net Start Delay
Net Start Delay

After the first drive on the network has been put on Auto mode, the network will
wait this amount of time before selecting and starting the Lead Drive.

0.0 ~

60.0 s

2.0 s

Programming

Description

Drive A

Drive B

Run Source: 1 = Terminals

b1-02 = 1

b1-02 = 1

Node Address

H5-01 = 1

H5-01 = 2

Highest Node Address

P9-25 = 2

P9-25 = 2

Pump Mode: 3 = Network

P1-01 = 3

P1-01 = 3

Feedback Source: 0 = Analog

P9-02 = 0

P9-02 = 0

Lag Fixed Speed

P9-06 = 54.0 Hz

P9-06 = 54.0 Hz

Setpoint

U1-01 = 100 psi

U1-01 = 100 psi

Start Level

P1-04 = 80 psi

P1-04 = 80 psi

* All other multiplexing and alternation parameters are at default settings.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

Drive A

CIMR-P7U40111-107

R+

S+

S-

R-

A2

AC

+V

A1

SN

S1

PRESSURE FEEDBACK

A

Drive B

CIMR-P7U40111-107

R+

S+

S-

R-

A2

AC

+V

A1

SN

S1

PRESSURE FEEDBACK B

RUN

RUN