Table 2.10, For c, Shunt connector cn15 – Yaskawa iQpump Controller User Manual User Manual

Page 49

Advertising
background image

2.3 Control Wiring

YASKAWA TM.iQp.06 iQpump Controller User Manual

49

◆ Shunt Connector CN15

The shunt connector CN15 is described in this section. The shunt connector along with parameters H4-07 and H4-08 select the signal
range of the analog output terminals FM and AM.

Shunt connector CN15 is only available when the optional Terminal Card with the 4-20 mA Analog Output Monitor is installed (Model

No. ETC618120). See

Chapter 7 Maintenance

, for installation of the optional Terminal Card.

The function of various shunt connector CN15 configurations is shown in

Table 2.10

.

Figure 2.5 Shunt Connector CN15 Location

Table 2.10 Shunt Connector CN15 Configuration Options

The software configuration for the analog output monitor signal type is listed below:

CN15

Analog Output Monitor Configurations

Voltage Output (0 - 10 Vdc) for terminals FM-AC (CH1) and AM-AC (CH2)

Current Output (4 ~ 20 mA) for terminals FM-AC (CH1) and AM-AC (CH2)

Voltage Output (0 - 10 Vdc) for terminals FM-AC (CH1)
Current Output (4 ~! 20 mA) for terminals AM-AC (CH2)

Current Output (4 ~ 20 mA) for terminals FM-AC (CH1)
Voltage Output (0 - 10 Vdc) for terminals AM-AC (CH2)

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

H4-07

0423

Terminal FM Signal Level
Selection
AO Level Select1

0: 0 - 10 Vdc
2: 4 ~ 20 mA*

0 or 2

0

Programming

H4-08

0424

Terminal AM Signal Level
Selection
AO Level Select2

0: 0 - 10 Vdc
2: 4 ~ 20 mA*
* An analog output of 4 ~ 20 mA cannot be used with the standard terminal
board. Therefore an optional terminal board (with shunt connector CN15)
is needed.

0 or 2

0

Programming