6.3 Alarm Detection

146

YASKAWA TM.iQp.06 iQpump Controller User Manual

LL3

Loss of Load Det 1

(Flashing)

Loss of Load Detection 1

iQpump output current < L6-02 for more than the

time set in L6-03.

Motor is underloaded.

Ensure the values in L6-02 and

L6-03 are appropriate.
Check application / machine
status to eliminate fault.

oH

Heatsnk Overtemp

(Flashing)

Cooling Fin / Cooling Fin Fan Overheat

The temperature of the iQpump cooling fin

exceeded the temperature programmed in
parameter L8-02.

Cooling fan(s) are not working, high

ambient temperature, a heating unit in

close proximity to iQpump is present.

Check for dirt build-up on the fans

and cooling fins.
Reduce the ambient temperature

around the iQpump.

iQpump Internal Cooling Fan.

Remove the heating unit.

oH2

Over Heat 2

(Flashing)

iQpump overheat pre-alarm signal is input from a
multi-function digital input terminal.

An external overheat condition exists

connected to one of the multi-function

input terminals S3, S4, S5, S6 or S7.

Check for an external condition.
Verify the program parameters

H1-01 thru H1-05.

oH3

Motor Overheat 1

(Flashing)

Motor Overheating Alarm

The iQpump stops or continues operation
according to the setting of L1-03.

Overheating of motor.

Recheck the cycle time and the
size of the load.
Recheck the accel / decel time

(C1-01 to C1-06).
Recheck the V/f pattern (E1-01

thru E1-13).
Recheck the motor rated current
value (E2-01).
Check the digital operator

connector.
Verify the setting of o2-06.

ov

DC Bus Overvolt

(Flashing)

DC Bus Overvoltage

208-240 Vac: Trip point is

≥ 400 Vdc.

480 Vac: Trip point is

≥ 800 Vdc.

High input voltage at R/L1, S/L2 and

T/L3.

Check the input circuit and reduce

the input power to within
specifications.
Extend the time in C1-02, C1-04,

or C1-06.

The deceleration time is set too short.

Power factor correction capacitors are

being used on the input to the

iQpump.

Remove the power factor
correction capacitors.

PrHT

Motor Preheating

Motor Preheating

Motor is preheating.

Motor Preheat 2 input is closed.

Uv

DC Bus Undervolt

(Flashing)

DC Bus Undervoltage

The DC bus voltage is

≤ L2-05.

208-240 Vac: Trip point is

≤ 190 Vdc.

480 Vac: Trip point is

≤ 380 Vdc.

Low input voltage at R/L1, S/L2 and

T/L3.

Check the input circuit and

increase the input power to within
specifications.

The acceleration time is set too short.

Extend the time in C1-01,

C1-03, or C1-05.

Voltage fluctuation of the input power

is too large.

Check the input voltage.

Uv2

CTL PS Undervolt

Control Power Supply Undervoltage of the control
circuit when running.

External load connected pulling down
the iQpump power supplies.

Cycle power off and on to the
iQpump.
Repair or replace the Power PCB /

Gate iQpump PCB.

Uv3

MC Answerback

Soft Charge Circuit Fault

The pre-charge contactor opened while the iQpump

was running.

Contacts on the soft charge contactor

are dirty and the soft charge contactor
does not function mechanically.

Cycle power off and on to the

iQpump.
Check the condition of the soft
charge contactor.

Digital Operator

Display

Description

Cause

Corrective Action