G.4 Sleep/Sleep Boost Function

YASKAWA

TM.iQp.06 iQpump Controller User Manual

245

G.4

Sleep/Sleep Boost Function

The following is a summary of a set-up procedure and application examples included in this section.

• Sleep/Sleep Boost Function

This function is intended for use with a pressure tank and will boost the set pressure (psi) over the Auto Setpoint Monitor (U1-01) prior to
shutdown (sleeping), extending the pump sleep time to reduce cycling and save energy.

Application

Example: Irrigation System

A customer is using a pressure tank within the system to compensate for small leaks in the system and to reduce the pump cycling during

very low demand periods.

• System Setpoint = 100 psi
• Transducer Range 4 ~ 20 mA = 300 psi

• Sleep Boost Requirement = 10 psi for 15 s
• Motor FLA = 10 Amps

Figure G.2

Figure G.4 Irrigation System Example

Related Parameters

The required parameter changes for the Sleep/Sleep Boost Function are as follows:

Note:

All other parameters are to remain at the factory default settings.

Parameter

Parameter Name

Setting

E2-01

Motor Rated Current

10 Amps

P1-03

Feedback Device Scaling

300 psi

P2-21

Sleep Boost Level

10 psi

P2-22

Sleep Boost Maximum Time

15 s

Monitor

Monitor Name

Setting

U1-01

Auto Setpoint Reference

100 psi

PRESSURE
TANK

TRANSDUCER

PUMP

MOTOR