5.3 Pump Protection

YASKAWA TM.iQp.06 iQpump Controller User Manual

131

5.3

Pump Protection

P2 Shutdown Pump System When Running at Low Speed (Sleep)

P2-01, P2-02, P2-03

To protect the pump from operating at very low speeds causing excessive pump wear the iQpump drive offers a function to shutdown
(Sleep) the pump system.

Select Signal to Monitor

The system level to monitor no-flow operation can be selected with parameter

P2-01 Sleep Level Type

:

Table 5.9

Setup Sleep Level (P2-02)

Sleep Detection level can be setup with

P2-02 Sleep Level

. The Sleep Level units for P2-02 depend on the selection of parameter P2-01

(System Units).

Parameter

No.

Address

Hex

Parameter Name

Digital Operator

Display

Description

Range Default

Menu

Location

P2-01

060A

Sleep Level Type
Sleep Lvl Type

Sets the sleep type.
0: Output Frequency
1: Output Current
2: Feedback
3: Output Speed (rpm)

<0034>

4: Low Flow (Terminal A1 - Flow meter required)

<0034>

Note:

Feedback depends on PID direction operation.

Displays a “Sleep” Alarm when active.

0 ~ 4

0

Programming

P2-02



060B

Sleep Level
Sleep Level

Sleep activates when selected level (P2-01) reaches programmed sleep level
for time specified in P2-03. The level type is determined by
P2-01. A value of 0 disables this function. This function is only active
during running while operating in auto mode.
If P1-01 = 3, the function is active when there is only one drive running on
the network.

<0034>

Display Units for Sleep Level P2-02 when P2-01 is programmed for the
following:
P2-01 = 0: Display based on “Hz”
P2-01 = 1: Display based on “A”
P2-01 = 2: Display based on P1-02 Selection
P2-01 = 3: Display based on “rpm”

<0034>

P2-01 = 4: Display based on P6-02 Selection

<0034>

Note:

When P2-01 is set for a value of 2, display units will be dependent on

P1-02 setting. If P2-02 = 0, pump will sleep at minimum speed.

0.0 ~

6000.0

0.0

Programming

P2-03



060C

Sleep Delay Time
Sleep Delay Time

Delay time before tje drive enters sleep mode when criteria is met as
defined by parameter P2-02.

0 ~ 3600

5 s

Programming

