Advertising
background image

4.2 iQpump Drive Quick Start-Up Procedures

84

YASKAWA TM.iQp.06 iQpump Controller User Manual

Figure 4.9

START LEVEL

Start Pump System

Start

Delay

200 PSI

Start Level P1-04 (Absolute)
(Example 100 PSI)

System Set-Point
(Example 150 PSI)

Feedback Signal from

pressure transducer

(4 – 20 mA)

0

Time

Pr

e

s

s

u

re

Start Level Delay (P1-05)

(Example 5.0 sec.)

Feedback Scaling (P1-03)
(Example 200 PSI)

SLEEP MODE (Example)

Minimum Speed P1-06
(Example 40.0 Hz)

Output

Frequency

(pump motor

speed)

0

Sleep Delay Time (P2-03)

(Example 5.0 sec.)

Ramp or Coast to Stop, b1-02

O

u

tp

ut

F

requenc

y

60 Hz

Pump Running

Go to Sleep

Time

WAIT FOR PRESSURE TO FALL BELOW

START LEVEL (P1-04)

WAIT

SYSTEM STARTS WHEN

PRESSURE SIGNAL

FALLS BELOW 100 PSI

SYSTEM GOES TO SLEEP

WHEN PUMP MOTOR SPEED

DROPS BELOW 2400 RPM

2

3

Start Pump System

Start

Delay

200 PSI

System Set-Point
(Example 150 PSI)

Feedback Signal from

pressure transducer

(4 – 20 mA)

0

Time

Pr

e

s

s

u

re

Start Level Delay (P1-05)

(Example 5.0 sec.)

Feedback Scaling (P1-03)
(Example 200 PSI)

WAIT

SYSTEM STARTS WHEN

PRESSURE SIGNAL

FALLS BELOW 100 PSI

Start Level P1-04 (Delta)
(Example -50 PSI,
Start Level = 150 – 50 = 100 PSI)

Example: Absolute Level (Positive Start Level)

Example: Delta Level (Negative Start Level)

Note: When System Set-point is changed, the start level is automatically adjusted .

-50 PSI

100 PSI

100 PSI

150

150