H3-10 terminal a2 gain setting, Pump tuning – Yaskawa iQpump Controller User Manual User Manual

Page 115

Advertising
background image

Pump Tuning

YASKAWA TM.iQp.06 iQpump Controller User Manual

115

Function: Aux Reference

Setting: 2

In order for the A2 analog input to be used as the master Speed Command, parameter H3-09 must be set for Aux Reference (H3-09 = “2:

Aux Reference”). Once A2 is configured as an auxiliary reference, it can be selected as the master Speed. Command by setting H3-13 =
“1: Main Fref TA2.” If H3-09 = 2, terminal A2 analog input will become the speed command when a digital input programmed for Multi-
Step Ref 1 (H1-0x = 3) is selected by a contact closure.

Function: PI Feedback

Setting: B

Configuring the A2 analog input as PI Feedback (H3-09 = “B: PI Feedback”) is a requirement of setting the iQpump drive up for PI

operation. The A2 analog input is the only source for feedback for PI operation though the setpoint can come from a number of different
sources (refer to the section covering the PI parameters for more information regarding specifying the setpoint source. PI parameters are
listed in section b5).

Parameters H3-10 (Terminal A2 Gain) and H3-11 (Terminal A2 Bias) can be used to configure the A2 analog input to match the signal
from the Feedback Transmitter.

The U1-24 monitor (PI Feedback) can be used to check the PI Feedback level with the digital operator.

Function: Frequency Bias 2

Setting: D

By setting H3-09 = “D: Frequency Bias 2,” the A2 analog input will serve as a bias signal to the A1 Speed Command. This setting
functions the same as a setting of H3-09 = 0: Frequency Bias.

Figure 5.43 Frequency Bias 2 Applied to Analog Speed Command

Function: PI Differential

Setting: 16

Normal PI operation will adjust the iQpump drive output in order to match the measured feedback value to a desired setpoint. When PI is
operated in the differential mode, however, the iQpump drive output is adjusted in order to maintain a desired differential between two

feedback signals.

When the A2 analog input is configured as a PI Differential (H3-09 = “16: PI Differential”), the A1 analog input becomes the other PI
Differential input. The desired differential is set by parameter b5-07 (PI Differential Setpoint) and can be set so that A2 is held less than

A1 (b5-07 < 0) or A2 is held greater than A1 (b5-07 > 0).

When PI Differential operation is chosen, the A1 feedback level can be monitored by U1-24 (PI Feedback) and the A2 feedback level can
be monitored by U1-53 (PI Feedback2).

Function: Not Used

Setting: 1F

When H3-09 = “1F: Not Used,” any signal applied to the A2 analog input will be ignored by the iQpump drive.

H3-10 Terminal A2 Gain Setting

Setting Range: 0.0 ~ 1000.0 %
Factory Default: 100.0 %

Factory Default

S

p

eed

C

o

mmand

10V

A1 Voltage

S

peed

C

o

mmand

A1 Voltage

10V

H3-03

H3-02

With H3-03 applied

S

peed

A1 Voltage

10V

With both H3-03 and analog input bias

(H3-09=0) applied

H3-02

H3-03

Sp

e

e

d

C

o

m

m

and

Sp

e

e

d

C

o

mma

n

d

Sp

e

e

d

C

o

m

m

and

(H3-09 = D) applied