Low City Pressure Input
Select
Low City In Sel

Selects the type of pressure switch connected to the “Low City
Pressure” digital input (H1-0x = 73).
0: Normally Open (closed indicates the “Low City Pressure”
condition)
1: Normally Closed (open indicates the “Low City Pressure”
condition)

0 ~ 1

1

Programming

P4-22



<0034>

835

Low City Pressure Input
Delay
Low City Delay

Sets the amount of time a “Low City Pressure” condition needs to be
present before the drives will stop. Also sets the amount of time that
the pressure needs to be adequate before the drive system will re-start.

1 ~ 1000 s

10 s

Programming

P4-23



<0034>

836

Lube Pump Delay Timer
Lube Pump Time

Sets the amount of time the drive’s output will be delayed and the Lube
Pump digital output (H2-0x = 55) will be energized.
A setting of zero will disable this feature.

0.0 ~

300.0 s

0.0 s

Programming

Hand Mode

P5-01



0124

Hand Mode Reference
Source
Hand Mode Ref

Sets the hand mode reference source.
0: Analog Input A1 (0-10 V)
1: Hand reference (P5-02)

0 ~ 1

1

Programming

P5-02



0125

Hand Reference
Hand Reference

Sets the frequency reference used when the hand mode is active and
P5-01 is programmed to 1.

0.00 ~

120.00 Hz 40.00 Hz Programming

P5-03

<0032>

0114

HAND / AUTO During
Run Selection
HAND/AUTO @Run

Selects if the drive will permit switching between HAND and AUTO
modes while running.
0: Disabled
1: Enabled
Switching from HAND to AUTO is not permitted when the drive
output frequency is less than the PID minimum speed.
Switching from AUTO to HAND is not permitted when the drive is
running in the multiplex mode with auxiliary drives enabled.

0 ~ 1

0

Programming

P5-04

<0032>

0513

Hand Key Function
Selection
Oper HAND Key

Enables or disables the “HAND” key on the digital operator.
0: Disabled
1: Enabled

0 ~ 1

1

Pump Quick

Setup

Flow Meter Setup

P6-01

<0034>

840

Flow Meter Scaling
Flow Meter Scale

Sets the scaling for the flow meter connected to Terminal A1. Enter the
gal / min when the flow meter is at it’s rated output.
A setting of 0.0 disables all flow meter functions.

0.0 ~

6000.0

Gpm

0.0 Gpm Programming

P6-02

<0034>

841

Water Flow Units
Water Flow Units

Sets the units displayed for monitor U1-95. Also sets units for
parameters P2-02 and P6-04.

0: U.S. Gallons / min (GPM)
1: U.S. Gallons / hr (GPH)
2: U.S. Barrels / min (BPM)
3: U.S. Barrels / hr (BPH)
4: U.S. Barrels / Day (BPD)

0 ~ 4

0

Programming

P6-03



<0034>

842

Flow Accumulation
Reset
Flow Accum Reset

Resets the accumulated flow and returns the monitors U1-96 and
U1-97 to zero.
0: No Reset
7770: Reset Accum
All other settings will have no effect.

Note:

After this parameter is changed it will automatically return to a

“0”.

0 ~ 65535

0

Programming

P6-04



<0034>

843

Low Flow Level
Low Flow Level

If the drive is running and the flow goes below this level for more than
the P6-05 time, a Low Flow fault or alarm will occur.
A setting of 0 disables the low flow detection.

If P1-03 = 3, a LOWFL fault will stop all drives running on the
network.

0.0 ~

6000.0

(*n1)

0.0

Programming

P6-05



<0034>

844

Low Flow Detection
Delay Time When
Already Running
Low Flow Tim Run

Sets the amount of time the flow rate must be below the P6-04 level
before a Low Flow condition is detected.

0 ~ 6000 s

10 s

Programming

P6-06



<0034>

845

Low Flow Detection
Wait Time At Start
Low Flow Time St

Sets the time the drive will wait after coming out of a zero speed
condition before activating Low Flow detection.

0.0 ~

3600.0 min

0.0 min Programming

(*n1) Displayed units are determined by parameter P6-02.


Denotes that parameter can be changed when the drive is running.