2 iqpump keypad messages, Iqpump keypad messages, Pump fault and alarm messages – Yaskawa iQpump Controller User Manual User Manual

Page 143

Advertising
background image

6.2 iQpump Keypad Messages

YASKAWA TM.iQp.06 iQpump Controller User Manual

143

6.2

iQpump Keypad Messages

Pump Fault and Alarm Messages

The iQpump has a comprehensive set of dedicated pump alarms and faults that will alert the operator when the pump system has
experienced any problems. A warning or fault message on the operator display indicates abnormal iQpump drive status.

Pump Fault Messages Generated

Table 6.2 Pump Fault Messages Generated

Digital Operator

Display

Description

Cause

Corrective Action

EF1-7

Pump Fault S#

External Pump Fault

Digital input is closed.

Check incoming digital signal from

external device.

FbL

Feedback Loss

<0032>

PI Feedback Loss

This fault occurs when PI

Feedback Loss Detection is

programmed to fault (b5-12
= 2) and the PI Feedback <

PI Feedback Loss Detection

Level (b5-13) for the PI
Feedback Loss Detection

Time (b5-14).

PI Feedback source (e.g. transducer, sensor,
building automation signal) is not installed

correctly or is not working.

Verify iQpump is programmed to
receive the PI Feedback source signal.

Check to ensure the PI Feedback
source is installed and working

properly.

HFb

High Feedback

High Feedback Fault

Feedback signal is too high.

The feedback level has risen above P1-09 level for

the time specified in P1-10. High feedback fault is
active in Hand Mode, Auto Mode, Pre-charge and

Thrust Mode when the drive is running.

Feedback level lower than the high
feedback level (P1-09).

LFb / LW

Low FB / Water

Low Feedback Level Fault

Feedback signal is too low or

water low input closed.

The feedback level has dropped below P1-07 for
the time specified in P1-08 or water low input is

active. Low feedback fault is active in Auto Mode

when the iQpump is running. Digital input is
closed.

Feedback level greater than the low

feedback level (P1-07). Check
incoming digital signal from external

device.

LoP

Loss of Prime

<0032>

Loss of Prime Fault

Pump has lost its prime.

If the output current drops below the P1-14 Prime
Loss Level for the time specified in P1-16 and the

output frequency is at fmax, a “Loss of Prime

(LOP)” fault occurs

Possible cause: Dry Well, Air in System, No Water

Allow system to pump water again
(must have resistance in pump).

nMS

Set Point Not Met

<0032>

Not Maintaining Set Point

Fault

Set Point cannot be
maintained.

When the setpoint cannot be maintained for a time

specified in P1-12, a “Not Maintaining Setpoint
(NMS)” fault occurs. The function is disabled

when the drive is not running and the PID is not

active.

Possible cause: Blocked Impeller, Over-Cycling,
Broken Pipe

Reduce the difference between the

setpoint and the feedback smaller than

the Maximum Setpoint Difference
(P1-11).

oPE12

<0032>

Thermostat Fault Selection
Fault

Both Normally Open (H1-xx = 83) and the

Normally Closed (H1-xx = 87) Thermostat Fault

inputs have been programmed

Only use one of the two fault inputs.

Advertising