DIP Switch S1

DIP Switch S1 is described in this section. The functions of DIP switch S1 are shown in

Table 2.9

.

Figure 2.4 DIP Switch S1 Location

Table 2.9 DIP Switch S1

Name

Function

Setting

S1-1

RS-485 and RS-422 terminating resistance

OFF: No terminating resistance (factory default)
ON: Terminating resistance of 110

Ω

S1-2

Input method for analog input A2

OFF: 0-10 Vdc (internal resistance: 20 k

Ω)

ON: 4 ~ 20 mA (internal resistance: 250

Ω) (factory default)