Figure 2.4, Dip switch s1 – Yaskawa iQpump Controller User Manual User Manual
Page 48
Advertising
2.3 Control Wiring
48
YASKAWA TM.iQp.06 iQpump Controller User Manual
◆ DIP Switch S1
DIP Switch S1 is described in this section. The functions of DIP switch S1 are shown in
Figure 2.4 DIP Switch S1 Location
Table 2.9 DIP Switch S1
Name
Function
Setting
S1-1
RS-485 and RS-422 terminating resistance
OFF: No terminating resistance (factory default)
ON: Terminating resistance of 110
Ω
S1-2
Input method for analog input A2
OFF: 0-10 Vdc (internal resistance: 20 k
Ω)
ON: 4 ~ 20 mA (internal resistance: 250
Ω) (factory default)
S1
O
1
Terminating
resistance
DIP Switch S1 located on
terminal board.
2
1
Advertising