Yaskawa iQpump Controller User Manual User Manual

Page 82

Advertising
background image

4.2 iQpump Drive Quick Start-Up Procedures

82

YASKAWA TM.iQp.06 iQpump Controller User Manual

Step # 5 - iQpump Drive Quick Setup Parameter Overview (Simplex)

Parameter

Value

Description

Reference

Comments

E2-01

Drive Size
Dependent

Motor Rated Current

Set to the motor nameplate full load amps.

For submersible motors use service
factor amps (SFA).

E2-04

2

Number of Motor Poles

Number of motor poles is used to show the correct motor RPM on the
display. Enter “4” for an 1800 RPM motor and “2” for a 3600 RPM
motor.

Confirm number of poles:

2 pole motor - 3600 RPM

4 pole motor - 1800 RPM

6 pole motor - 1200 RPM

8 pole motor - 900 RPM

P1-03

145

Feedback Device Scaling

System Scaling: Enter feedback device maximum.

Example: Enter 200 for pressure transducer with a maximum of 200 psi
at 20 mA.

Confirm feedback device scaling.

(See

Figure 4.8

)

d1-01

0

Setpoint 1

Set System Setpoint

Set to system pressure.

P1-04

0.0 psi

Start Level

When the iQpump is turned On and the feedback signal level
(transducer) falls below this level, the pump system will start after the
time specified in P1-05 (default 1 sec).

Programming the Start Level as an Absolute Value

Start Level has to programmed to a positive value in order for the Start
Level to be an absolute value. Example: Start Level P1-04 set to 50 PSI
and delay time P1-05 set to 5 sec. Pump system will start when the
pressure drops below 50 PSI for 5 sec.

Programming the Start Level as a Delta Level from the System
Setpoint

Start Level has to programmed to a negative value in order for the Start
Level to be a delta value from the setpoint.

Example: Start Level P1-04 set to –10 PSI with a system setpoint of 50
PSI and a delay time P1-05 set to 5 sec. Pump system will start when the
pressure drops below 40 PSI (50 - 10) for 5 sec.

It is mandatory to program the Start
Level in order to use the sleep
function.

(See

Figure 4.9

)

P1-06

40.0 Hz

Minimum Pump

Frequency

Minimum speed (Hz) the pump motor has to operate at.

Example: Base pump motor speed is 3600 RPM, minimum speed is
2400 RPM. Set the minimum pump frequency to 40.0 Hz
(2400 ÷ 3600 x 60 Hz = 40 Hz)

Minimum pump frequency should be
set to a value where the pump enters
the no-flow condition.

P4-10

0

Disabled

Auto Mode Operator Run

Power Down Storage

Stores the run status in the Auto Mode when operating from digital
operator (b1-02 = 0)

0: Disabled

1: Enabled

Recommended for use when Start /
Stop command is from keypad.

(

Refer to Auto Operation -

Power Down Storage on

page 86

)

P5-04

1

Enabled

Hand Key

Enable / Disable

Enables or disables the Hand Key on the digital operator.

0: Disabled

1: Enabled

Hand Key on keypad.

(See

Figure 4.10

)

b5-03

3.0 s

PI Integral Time

Decrease integral time to make iQpump more responsive.

NOTICE: May cause system
instability if this value is too low.

b5-12

2

(Fault)

PI Feedback Reference

Missing Detection

Selection

Select what to do when the feedback device (transducer) fails or gets
disconnected.

0: Disabled, continue running no message is displayed.

1: Alarm, show warning on the keypad when the feedback device fails
or is disconnected.

2: Fault, stop pump system when the feedback fails or is disconnected.

Note: Disable parameter b5-12 if no
transducer is installed.

Use to change the sign.

Advertising