4.2 iQpump Drive Quick Start-Up Procedures

YASKAWA TM.iQp.06 iQpump Controller User Manual

83

Figure 4.8

b5-14

2.0 s

PI Feedback Loss

Detection Time

Delay time before iQpump shows alarm or fault when feedback device
has failed or is disconnected. Example: 2.0 s, iQpump displays alarm or
fault 2 s after the device has failed or is disconnected.

C1-01

20.0 s

Acceleration Time 1

Time it takes to accelerate the pump motor from zero to maximum
speed.

Adjusted depending on system
performance.

C1-02

10.0 s

Deceleration Time 1

Time it takes to decelerate the plump motor from maximum speed to
zero.

L5-01

5

Number of Restart

Attempts

Determines the number of times iQpump will perform an automatic
restart on the faults listed in the comments column.

iQpump System Protection Faults that can be setup to restart are Low
Level Feedback, High Level Feedback, transducer Loss, Not
Maintaining Setpoint, Loss of Prime, PUmp Over Cycle. Refer to
parameters P4-07 and P4-08. The number of restart attempts is set by
L5-01.

Overcurrent

Ground Fault

Output Phase Loss

Input Phase Loss

iQpump Overload

L5-03

20 s

Maximum Restart Time

After Fault

If the restart fails (or is not attempted due to a continuing fault
condition), iQpump waits the Maximum Restart Time After Fault before
attempting another restart.

Motor Overload

Overtorque

DC Bus Fuse Blown

DC Bus Undervoltage

DC Bus Overvoltage

Overheat

P1-06

40.0 Hz

Minimum Pump

Frequency

Minimum speed (Hz) the pump has to operate at.

Example: Base pump motor speed is 3600 RPM, minimum speed is
2400 RPM. Set minimum pump frequency to 40.0 Hz
(2400 ÷ 3600 x 60 Hz = 40 Hz)

P1-06 should be set to the level where
the pump can produce the minimum
pressure even at zero flow.

P2-03

5 s

Sleep Delay Time

Time it takes before the pump system goes to sleep when the selected
signal level (P2-01) falls below the specified sleep level (P2-02

Adjust according to system
requirements.

P4-05

30.0 Hz

Thrust Bearing Frequency

Sets the frequency reference used when the thrust bearing function is
active. A value of 0 disables this function.

Primarily used for submersible
pumps. Program P4-05 = 0.0 Hz to
disable function when iQpump is used
with a centrifugal pump.
(See

Figure 4.11

)

P4-11

0.2 min

Utility Start Delay

When utility power is restored and P4-10 is enabled (1), iQpump waits
the time specified in P4-11 before auto operation becomes active.

Note: Only active when P4-10 is
enabled (1) and operation (start / stop)
is from the digital operator.

Parameter

Value

Description

Reference

Comments

Examples:

0 – 1000 , no decimals, P1-03 = 1000

0 – 300.0, one decimal, P1-03 = 10300

0 – 50.00, two decimals , P1-03 = 25000

P1-03 = 0 0 0 0 0 Feedback Scaling

Feedback

Maximum

Decimal Point

Position

TRANSDUCER / FEEDBACK DEVICE SCALING

1