G.10 First In First Out (FIFO) Description

G.10 First In First Out (FIFO) Description

The following is a summary of a set-up procedure and application examples included in this section.

• FIFO Description

iQpump Drive Alternation Parameters

Definitions

• First Drive: U1-62 = 1

• Last Drive: U1-62 = number of pumps running (Lead iQpump drive)
• FIFO: First In, First Out - First iQpump drive is alternated
• LIFO: Last In, First Out - Lead iQpump drive is alternated

Note:

In either FIFO or LIFO, the replacement iQpump drive always becomes the new Lead iQpump drive

Related Parameters

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

P9-03



0882

Alternation Time

Alternation Time

Specifies the time for a drive to request alternation, influenced by the Alternation
Mode P9-04. The request to alternate is made after this time expires. Active on the
First Drive for FIFO modes, and cumulative on the Lead drives for LIFO mode.

0 ~ 1000 h

24 h

Programming

P9-04

0883

Alternation Mode

Alternation Mode

Determines how alternation is performed:
0: FIFO Auto: first iQpump drive is removed and there is no replacement unless it
is the only iQpump drive
1: FIFO Forced: first iQpump drive is removed and a new Lead iQpump drive is
brought on
2: LIFO: Lead iQpump drive is alternated with a new Lead iQpump drive
3: FIFO at Sleep: first iQpump drive is removed only when going to sleep

0 ~ 2

0

Programming

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

U1-68

0009C Time to Alternate

Time to Alternate

Time remaining before a drive requests alternation, which is dependent on P9-04. Pump requests for
alternation when this shows 0 min.

Advertising