1.7 Installation Orientation and Clearances

YASKAWA TM.iQp.06 iQpump Controller User Manual

29

1.7

Installation Orientation and Clearances

Install the iQpump drive vertically so as not to reduce the cooling efficiency. When installing the iQpump drive, always provide the

following installation clearances to allow normal heat dissipation. For 3HP, 208V / 240V (CIMR-P7U22P2-107 and below) or 2HP,
480V (CIMR-P7U41P-107 and below), ensure that the heatsink is against a closed surface to avoid diverting cooling air around the
heatsink.

Figure 1.12 iQpump Drive Installation Orientation and Clearance

IMPORTANT

• The same clearance is required horizontally and vertically for both Open Chassis (IP00) and NEMA

Type 1 iQpump drives.

• Always remove the top and bottom protection covers before installing a CIMR-P7U2018 / 4018-107

and smaller iQpump drive in a panel. Always provide enough clearance for lifting eye bolts and the
main circuit wiring when installing a CIMR-P7U2022 / 4030-107 and larger iQpump drive in a panel.

4.75 in (120 mm. minimum)

4.75 in (120 mm. minimum)

Air

Air

Vertical Clearance

Horizontal Clearance

1.2 in

(30.5 MM.) min.

1.2 in

(30.5 mm. minimum)

1.2 in

(30.5 mm. minimum)

4.75 in (50 mm. minimum)

4.75 in (120 mm. minimum)