E.2 branch circuit overload protection, E.3 peripheral devices, Magnetic contactor – Yaskawa iQpump Controller User Manual User Manual

Page 230: Caution, 230 yaskawa, Table e.4 semiconductor fuses for drive i

Advertising
background image

230

YASKAWA

TM.iQp.06 iQpump Controller User Manual

E.2 Branch Circuit Overload Protection

Table E.4 Semiconductor Fuses for drive I

2

t Protection and Branch Circuit Short Circuit Protection (400V Series)

E.2

Branch Circuit Overload Protection

All iQpump drive models have built-in UL evaluated motor overload protection. Motor overload protection is also provided in

accordance with the NEC and CEC. Additional branch circuit overload protection is not required for single motor applications.

E.3

Peripheral Devices

The following peripheral devices may need to be mounted between the AC power supply and the iQpump drive input terminals R/LI, S/

L2, and T/L3.

For more details on peripheral devices, contact the manufacturer.

Magnetic Contactor

Mount a surge protector on the coil. When using a magnetic contactor to start and stop the iQpump drive, do not exceed one start per
hour.

Table E.4 Semiconductor Fuses for drive I

2

t Protection and Branch Circuit Short Circuit Protection (400V Series)

Drive Model

CIMR-P7U

-

107

Recommended

Alternate 1

Alternate 2

Fuse Mfr.

Model No.

Rating

Fuse Mfr.

Model No.

Rating

Fuse Mfr.

Model No.

Rating

40P4

Ferraz

A60Q10-2

600V, 10A

Ferraz

A070GRB006T13

700V, 6A

Ferraz

A70QS16-14F

690V, 16A

40P7

Ferraz

A60Q10-2

600V, 10A

Ferraz

A070GRB006T13

700V, 6A

Ferraz

A70QS16-14F

690V, 16A

41P5

Ferraz

A60Q12-2

600V, 12A

Ferraz

6,900CPGRC14.51/25

690V, 25A

Ferraz

A70QS20-14F

690V, 20A

42P2

Ferraz

A60Q15-2

600V, 15A

Ferraz

A70QS25-22F

700V, 25A

Ferraz

A70QS20-14F

690V, 20A

43P7

Ferraz

A60Q20-2

600V, 20A

Ferraz

A70QS20-14F

700V, 20A

Ferraz

A70QS25-14F

690V, 25A

44P0

Ferraz

A60Q30-2

600V, 30A

Ferraz

A70QS32-14F

700V, 32A

Ferraz

A70QS40-14F

690V, 40A

45P5

Ferraz

A60Q30-2

600V, 30A

Ferraz

A70QS32-14F

700V, 32A

Ferraz

A70QS40-14F

690V, 40A

47P5

Ferraz

A60Q30-2

600V, 30A

Ferraz

A70QS40-14F

700V, 40A

-

-

-

49P0

Ferraz

A70P50-4

700V, 50A

Ferraz

A50QS50-4

500V, 50A

Bussmann

FWH-80B

500V, 80A

4011

Ferraz

A70P50-4

700V, 50A

Ferraz

A50QS50-4

500V, 50A

Bussmann

FWH-80B

500V, 80A

4015

Ferraz

A70P70-4

700V, 70A

Ferraz

A50QS80-4

500V, 80A

Bussmann

FWH-100B

500V, 100A

4018

Ferraz

A70P80-4

700V, 80A

Ferraz

A50QS100-4

500V, 100A

Bussmann

FWH-125B

500V, 125A

4022

Ferraz

A70P80-4

700V, 80A

Ferraz

A50QS100-4

500V, 100A

Bussmann

FWH-125B

500V, 125A

4024

Ferraz

A70P100-4

700V, 100A

Ferraz

A50QS125-4

500V, 125A

Bussmann

FWH-125B

500V, 125A

4030

Ferraz

A70P100-4

700V, 100A

Ferraz

A50QS125-4

500V, 125A

Bussmann

FWH-125B

500V, 125A

4037

Ferraz

A70P125-4

700V, 125A

Ferraz

A50QS125-4

500V, 125A

Bussmann

FWH-150B

500V, 150A

4045

Ferraz

A70P150-4

700V, 150A

Ferraz

A50QS150-4

500V, 150A

Bussmann

FWH-175B

500V, 175A

4055

Ferraz

A70P200-4

700V, 200A

Ferraz

A70QS200-4

700V, 200A

Bussmann

FWH-200B

500V, 200A

4075

Ferraz

A70P250-4

700V, 250A

Ferraz

A50QS250-4

500V, 250A

Bussmann

FWH-250A

500V, 250A

4090

Ferraz

A70P300-4

700V, 300A

Ferraz

A50QS300-4

500V, 300A

Bussmann

170M4611

690V, 350A

4110

Ferraz

A70P350-4

700V, 350A

Ferraz

A50P350-4

500V, 350A

Bussmann

170M4611

690V, 350A

4132

Ferraz

A70P400-4

700V, 400A

Ferraz

A70P500-4

700V, 500A

Bussmann

170M5610

690V, 500A

4160

Ferraz

A70P450-4

700V, 450A

Ferraz

A70QS700-4

700V, 700A

Bussmann

FWH-600A

500V, 600A

4185

Ferraz

A70P600-4

700V, 600A

Ferraz

A70QS700-4

700V, 700A

Bussmann

FWH-700A

500V, 700A

4220

Ferraz

A70P700-4

700V, 700A

Bussmann

FWH-800A

500V, 800A

Bussmann

FWH-1000A

500V, 1000A

4300

Ferraz

A70P900-4

700V, 900A

Bussmann

FWH-1000A

500V, 1000A

Bussmann

FWH-1200A

500V, 1200A

CAUTION

Never connect a general LC/RC noise filter to the iQpump drive output circuit.
Never connect a phase-advancing capacitor to the input or output sides, or a surge suppressor to the output side of the
iQpump drive. When magnetic contactor is installed between the iQpump drive and the motor, never turn it on or off
during operation.

Advertising