Pump Tuning

YASKAWA TM.iQp.06 iQpump Controller User Manual

113

Figure 5.24

Figure 5.39 Connection of a 3-Wire 4~20 mA Feedback Device (H3-08 = 2)

The H3-08 parameter (Terminal A2 Signal Level) allows the programmer to specify the signal that will be applied to the A2 analog input.

The A2 analog input can accept either a 0–10 Vdc or 4 ~ 20 mA signal as a reference. The iQpump drive also has a DIP switch (S1) on
the removable terminal board that must be set for the proper reference signal into the A2 analog input. The S1-2 DIP switch setting
determines the internal resistance of the A2 input while parameter H3-08 determines how the iQpump drive interprets the measured

signal.

Figure 5.25

Figure 5.26

Figure 5.40 DIP Switch S1

Table 5.4 DIP Switch S1

Name

Function

Setting

S1-1

RS-485 and RS-422 terminating resistance

OFF: No terminating resistance
ON: Terminating resistance of 110

Ω

S1-2

Input method for analog input A2

OFF: 0 ~ 10 V (internal resistance: 20 k

Ω)

ON: 4 ~ 20 mA (internal resistance: 250

Ω) (Default)

S1

O

1

Terminating
resistance

DIP Switch S1-1 located on
terminal board.

2

1