5.3 Pump Protection

YASKAWA TM.iQp.06 iQpump Controller User Manual

133

Sleep Function Based on Output Current (P2-01 = 1)

The iQpump drive enters sleep mode when output current falls below level programmed in P2-02 for a time specified in P2-03.

Figure 5.35

Figure 5.53 Sleep Function Based on Output Current

Start Level Delay

P1-05

Start Level Delay

P1-05

Sleep Delay Time

P2-03

Output Frequency

Sleep Level

P2-02

Min. Frequency

P1-06

STOP, 0Hz

Feedback

Timing Chart: Start Level Operation

System

Set-Point

Start Level

P1-04

0%

Auto Mode Run

OFF Mode

Sleep Active

Wait for Start

Start System

AUTO MODE RUN

AUTO MODE RUN

AUTO MODE RUN

SLEEP ACTIVE

Start System, Incoming Run Command

TIME

START
DELAY

START DELAY

Output Current