6.1 Fault Detection

YASKAWA TM.iQp.06 iQpump Controller User Manual

139

CPF08

WAT-Err

Watchdog Timer Fault

(WAT)

Cycle power off and on to the iQpump.

Control circuit damage.

Replace the iQpump.

CPF09

CPU-Err

CPU-ASIC Mutual Diagnosis Fault

(COY)

Cycle power off and on to the iQpump.

Control circuit damage.

Replace the iQpump.

CPF10

ASIC-Err

ASIC Version Fault

(ASIC)

Control circuit damage.

Replace the iQpump.

CPF20

Option A/D Error

Option Card Fault

Option card connector connection

fault.

Remove all inputs to the option board.

Option card A/D converter fault.

Perform a factory initialization.
Cycle power off and on to the iQpump.
Replace the option board.
Replace the control board.

CPF21

Option CPU Down

Self-diagnosis Fault of Communication Option
Card

Noise or spike on the

communication line, defective

option board.

Perform a factory initialization.
Cycle power off and on to the iQpump.
Replace the option board.
Replace the control board.

CPF22

Option Type Err

Communication Option Card Code Number Fault

Unrecognizable option board is

connected to the control board.

Remove any option boards.
Cycle power off and on to the iQpump.
Perform a factory initialization.
Replace the option board.
Replace the control board.

CPF23

Option DPRAM Err

Communication Option Card Interconnection

Fault

An option board is not correctly

connected to the control board or

an option board that is not made for
the iQpump is attached to the

control board.

Remove power to the iQpump.
Connect the option board once more.
Perform a factory initialization.
Cycle power off and on to the iQpump.
Replace the option board.
Replace the control board.

EF0

Opt External Flt

Communication Option Card External Fault

An external fault condition exists.

Check for an external condition.
Verify the parameters.
Verify communication signal.

EF3

Ext Fault S3

External Fault at Terminal S3

An external fault condition exists
connected to a multi-function

digital input.

Eliminate the cause of an external fault
condition.

EF4

Ext Fault S4

External Fault at Terminal S4

EF5

Ext Fault S5

External Fault at Terminal S5

EF6

Ext Fault S6

External Fault at Terminal S6

EF7

Ext Fault S7

External Fault at Terminal S7

Remove the fault from a multi-function
digital input.

FbL

Feedback Loss

PI Feedback Loss

This fault occurs when PI Feedback Loss

Detection is programmed to fault (b5-12 = 2) and
the PI Feedback < PI Feedback Loss Detection

Level (b5-13) for the PI Feedback Loss Detection

Time (b5-14).

PI Feedback source (e.g.
transducer, sensor, building

automation signal) is not installed

correctly or is not working.

Verify iQpump is programmed to receive

the PI Feedback source signal.

Check to ensure the PI Feedback source
is installed and working properly.

GF

Ground Fault

Output Ground Fault

iQpump output grounding current has exceeded

50 % of the iQpump rated output current.

Motor lead is shorted to ground,
DCCT defective.

Remove the motor and run the iQpump

without the motor.
Check the motor for a phase-to-ground
short.
Check the output current with a clamp

on meter to verify the DCCT reading.

Digital

Operator Display

Description

Cause

Corrective Action