222

YASKAWA

TM.iQp.06 iQpump Controller User Manual

D.3 Modbus Data Tables

002B

Sequence input status

Bit 0

Input terminal S1 1: ON 0: OFF

Bit 1

Input terminal S2 1: ON 0: OFF

Bit 2

Multi-function digital input terminal S3 1: ON 0: OFF

Bit 3

Multi-function digital input terminal S4 1: ON 0: OFF

Bit 4

Multi-function digital input terminal S5 1: ON 0: OFF

Bit 5

Multi-function digital input terminal S6 1: ON 0: OFF

Bit 6

Multi-function digital input terminal S7 1: ON 0: OFF

Bits 7 to F

Not used

002C

Drive status

Bit 0

Operation 1: Operating

Bit 1

Zero speed 1: Zero speed

Bit 2

Frequency agree 1: Matched

Bit 3

Desired frequency agree 1: Matched

Bit 4

Frequency detection 1 1: Output frequency

≤ L4-01

Bit 5

Frequency detection 2 1: Output frequency

≥ L4-01

Bit 6

Drive startup completed 1: Startup completed

Bit 7

Low voltage detection 1: Detected

Bit 8

Baseblock 1: Drive output baseblock

Bit 9

Frequency reference mode 1: Not communication 0: Communication

Bit A

Run command mode 1: Not communication 0: Communication

Bit B

Overtorque detection 1: Detected

Bit C

Frequency reference lost 1: Lost

Bit D

Retrying error 1: Retrying

Bit E

Error (including Modbus communications time-out) 1:Error occurred

Bit F

Modbus communications time-out 1: Timed out

002D

Multi-function digital output status

Bit 0

Multi-function digital output 1 (terminal M1-M2) 1: ON 0: OFF

Bit 1

Multi-function digital output 2 (terminal M3-M4): 1: ON 0: OFF

Bit 2

Not used

Bits 3 to F

Not used

002E - 0030

Not used

0031

Main circuit DC voltage

0032 - 0037

Not used

0038

PI feedback level (Input equivalent to 100 % / Max. output frequency; 10/1%; without sign)

0039

PI input level (±100%/±Max. output frequency; 10/1 %; with sign)

003A

PI output level (±100%/±Max. output frequency; 10/1 %; with sign)

003B

CPU software number

003C

Flash software number

003D

Communication error details

Bit 0

CRC error

Bit 1

Invalid data length

Bit 2

Not used

Bit 3

Parity error

Bit 4

Overrun error

Bit 5

Framing error

Bit 6

Time-out

Bits 7 to F

Not used

003E

KVA setting

003F

Control method

Note: Communication error details are stored until an error reset is input (errors can be reset while the drive is operating).

Register No.

(Hex)

Contents