Pump Tuning

YASKAWA TM.iQp.06 iQpump Controller User Manual

109

E1-06 Base Frequency

Setting Range: 0.0 ~ 200.0 Hz
Factory Default: 60.0 Hz

E1-07 Mid Output Frequency A

Setting Range: 0.0 ~ 200.0 Hz

Factory Default: 3.0 Hz

E1-08 Mid Output Voltage A

Setting Ranges: 0.0 ~ 255.0 V (240 V Models)

Setti ng Ranges:

0.0 ~ 510.0 V (480 V Models)

Factory Defaults:17.2 V (240 V Models)

Factory Defaults:

34.5 V (480 V Models)

E1-09 Minimum Output Frequency

Setting Range: 0.0 ~ 200.0 Hz
Factory Default: 1.5 Hz

E1-10 Mid Output Voltage

Setting Ranges: 0.0 ~ 255.0 V (240 V Models)

Setting Ranges:

0.0 ~ 510.0 V (480 V Models)

Factory Defaults: 10.3 V (240 V Models)

Factory Defaults:

20.7 V (480 V Models)

E1-11 Mid Output Frequency B

Setting Range :0.0 ~ 120.0 Hz
Factory Default: 0.0 Hz

E1-12 Mid Output Voltage B

E1-13 Base Voltage

Setting Ranges: 0.0 ~ 255.0 V (240 V Models)

Setting Ranges:

0.0 ~ 510.0 V (480 V Models)

Factory Defaults:0.0 V (All Models)

To set up a custom V/f pattern, program the points shown in the diagram below using parameters E1-04 through E1-13. Be sure that the
following condition is true: E1-09

E1-07

E1-06

E1-11

E1-04.