Page 109

Pump Tuning
YASKAWA TM.iQp.06 iQpump Controller User Manual
109
■
E1-06 Base Frequency
Setting Range: 0.0 ~ 200.0 Hz
Factory Default: 60.0 Hz
■
E1-07 Mid Output Frequency A
Setting Range: 0.0 ~ 200.0 Hz
Factory Default: 3.0 Hz
■
E1-08 Mid Output Voltage A
Setting Ranges: 0.0 ~ 255.0 V (240 V Models)
Setti ng Ranges:
0.0 ~ 510.0 V (480 V Models)
Factory Defaults:17.2 V (240 V Models)
Factory Defaults:
34.5 V (480 V Models)
■
E1-09 Minimum Output Frequency
Setting Range: 0.0 ~ 200.0 Hz
Factory Default: 1.5 Hz
■
E1-10 Mid Output Voltage
Setting Ranges: 0.0 ~ 255.0 V (240 V Models)
Setting Ranges:
0.0 ~ 510.0 V (480 V Models)
Factory Defaults: 10.3 V (240 V Models)
Factory Defaults:
20.7 V (480 V Models)
■
E1-11 Mid Output Frequency B
Setting Range :0.0 ~ 120.0 Hz
Factory Default: 0.0 Hz
■
E1-12 Mid Output Voltage B
E1-13 Base Voltage
Setting Ranges: 0.0 ~ 255.0 V (240 V Models)
Setting Ranges:
0.0 ~ 510.0 V (480 V Models)
Factory Defaults:0.0 V (All Models)
To set up a custom V/f pattern, program the points shown in the diagram below using parameters E1-04 through E1-13. Be sure that the
following condition is true: E1-09
≤
E1-07
≤
E1-06
≤
E1-11
≤
E1-04.