Pump Tuning

108

YASKAWA TM.iQp.06 iQpump Controller User Manual

Table 5.3 Preset V/f Patterns

If one of the custom V/f patterns is selected, then parameters E1-04 through E1-13 will determine the V/f pattern.

Table 5.3

is for 240V class units only. For 480V class units multiply the voltage value by 2.

Important: When a factory Initialization is performed, the setting of E1-03 is unaffected but the settings of E1-04 through E1-13 are

returned to their factory default settings.

E1-04 Maximum Output Frequency

Setting Range: 0.0 ~ 120.0 Hz
Factory Default: 60.0 Hz

E1-05 Maximum Output Voltage

Setting Ranges: 0.0 ~ 255.0 V (240 V Models)

Setting Ranges:

0.0 ~ 510.0 V (480 V Models)

Factory Defaults: 230.0 V (240 V Models)

Factory Defaults:

460.0 V (480 V Models)

Specifications

E1-03

V/f Pattern *1

Specifications

E1-03

V/f Pattern *1

General-

purpose

50 Hz

0

High

Starting

Torque *2

50 Hz

High Starting

Torque 1

8

High Starting

Torque 2

9

60 Hz Saturation

1

F

60 Hz

High Starting

Torque 1

A

50 Hz Saturation

2

High Starting

Torque 2

B

72 Hz

3

High Speed

Operation

90 Hz

C

Variable

Torque

50 Hz

Variable

Torque 1

4

120 Hz

D

Variable

Torque 2

5

60 Hz

Variable

Torque 1

6

Variable

Torque 2

7

(Hz)

(V)

230

17
10

0 1.3 2.5

50

0

230

(V)

28

22

15

13

(Hz)

0 1.3 2.5

50

9

8

(Hz)

0 1.5 3.0

50 60

17
10

2

1
F

(V)

230

230

(V)

28

22

17

13

(Hz)

0 1.5 3.0

B

A

60

(Hz)

0 1.5 3.0

60 72

17
10

3

(V)

230

(Hz)

0 1.5 3.0

60 90

17
10

C

(V)

230

230

(V)

57
40

10

9

(Hz)

0 1.3

25

50

5

4

(Hz)

0 1.5 3.0

60 120

17
10

D

(V)

230

230

(V)

57
40

10

9

(Hz)

0 1.5

30

60

7

6

Advertising