Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

311

9

"CAN on board" system bus

9.6

Process data transfer

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.6.5.1

Parameter setting

Short overview: Parameters for the synchronisation via sync telegram

Sync source

C01120

is used to select the source of the synchronisation signals. Only one source can synchronise

the node.

Sync cycle time
Time after which the internal phase-locking loop (PLL) anticipates the synchronisation signals. The

time must be set in

C01121

according to the cycle of the synchronisation source selected in

C01120

.

Example: For the system bus, the distance between two synchronisation signals is set to 2 ms. If the

system bus is to be used as synchronisation source, a sync cycle time of 2000 μs must be set in

C01121

.

Parameter

Info

Lenze setting

Assignment

Value Unit

Sync

master

Sync

slave

C00367

CAN SYNC Rx identifier

128

C00368

CAN SYNC Tx identifier

128

C00369/1

CAN sync transmission cycle time

0 ms

C01120

Sync source

Off

C01121

Sync cycle time

1000 μs

C01122

Sync phase position

400 μs

C01123

Sync tolerance

0 μs

C01124

Sync PLL increment

109 ns

C01130

Sync application cycle

1000 μs

Note!

If the synchronisation takes place via the system bus, it is reasonable to only enter

integer multiples of 1000 μs in

C01121

.