Running the quick motor tune procedure, Running the quick motor tune procedure -8 – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 106

Advertising
background image

6-8

Starting Up Your System

To begin the start up procedure from the Choose Mode/Startup
prompt, you need to follow these steps:

When you have finished the start up procedure and pressed

ENTER

,

you are placed at the following prompt:

To continue, press

ENTER

. To go back to the start up routine:

1. Press either INC or DEC to toggle Completed to Reset Sequence.

2. Press ENTER.

The 1336 IMPACT drive retains any information that you have
already entered. Choosing Reset Sequence lets you re-enter the start
up routine.

Running the Quick Motor Tune
Procedure

The Quick Motor Tune procedure helps you set up your basic drive
parameters, verify that your motor and encoder (if used) leads are
connected correctly, and run the auto-tune tests. You should set this
information up the first time you run the start up procedure.

Follow these steps to complete the Quick Motor Tune procedure:

Step:

At this prompt:

You need to:

Then go to:

1.

Choose Mode

Start Up

Press the

ENTER

key.

Step 2

2.

Quick Motor Tune

Procedure? Y

Decide if you want to run the Quick Motor Tune routine. The quick motor tune routine
includes entering your basic drive/motor nameplate data, verifying that your motor and
encoder (if used) leads are connected correctly, and running the auto-tune tests.

If yes, press the

ENTER

key.

Running the Quick
Motor Tune
Procedure

If no, press

INC

or

DEC

to get

N

. Then press

ENTER

.

Step 3

3.

Config Digital

Section? N

Decide if you need to configure the digital input and output parameters. The digital section
includes the set up information for the programmable relay and the L Option board.

If yes, press

INC

or

DEC

to get Y. Then press

ENTER

.

Configuring the
Digital Section

If no, press the

ENTER

key.

Step 4

4.

Setup Reference

Analog/PPR IO? N

Decide if you need to configure the analog input and output parameters. The analog
section includes the set up information for the following inputs and outputs: Speed
Reference 1, Speed Reference 2, Torque Reference, Analog Output 1, Analog Output 2,
and the HIM status display.

If yes, press

INC

or

DEC

to get Y. Then press

ENTER

.

Configuring the
Analog Section

If no, press

ENTER

.

Step 5

5.

Startup Complete

Press

ENTER

.

Advertising