Control Block Diagrams

The Limiter/Scaler function takes input from Iq % (parameter 91), the
torque reference, and Flux Current (parameter 168) and performs
limit checks and scaling on the two values. The Limiter/Scaler
function outputs the synchronous (or electrical) values of the torque
command (Iq

e

) and the flux current (Id

e

).

These values, Iq

e

and Id

e

, are converted to stationary values. To

convert the values, the conversion routine also takes input from the
feedback device.

Once the values are converted to stationary values, they are sent to the
current regulator.

file:

Motor/Inverter

group:

Motor Constants

file:

Monitor

group:

Motor Status

file:

Motor/Inverter

group:

Motor Nameplate
Encoder Data

If the feedback

device is:

Then:

Encoderless

The value of Motor Frequency (parameter 89) is integrated to get
the proper units and then used for the conversion.

Encoder

The drive uses the values of Motor Poles (parameter 7) and
Encoder PPR (parameter8) to adjust the value coming from the
encoder. The value of Slip Gain (parameter 169) is integrated to
get the proper units and then added to the value from the
encoder.