7motor poles, 8encoder ppr, 9service factor – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 209: 10 pwm frequency, 11 inverter amps, 12 inverter volts

Advertising
background image

Parameters

11-11

7

Motor Poles

Motor Poles contains the number of motor poles. The drive
calculates this value during the Quick Motor Tune portion of the
start up routine.

Note: Encoder PPR

Parameter number

7

File:group

Motor/Inverter:Motor Nameplate

Motor/Inverter:Motor Constants

Parameter type

destination

Display

x poles

Factory default

4 poles

Minimum value

2 poles

Maximum value

40 poles

Conversion

1 = 1

8

Encoder PPR

Encoder PPR contains the pulse per revolution rating of the
feedback device when you use an encoder to determine motor
speed.

Note: Encoder PPR

Parameter number

8

File:group

Motor/Inverter:Encoder Data

Control:Feedback Device

Parameter type

destination

Display

x ppr

Factory default

1024 ppr

Minimum value

calculated

Maximum value

20000 ppr

Conversion

1 = 1

9

Service Factor

Enter the minimum level of current that causes a motor overload
(I

2

T) trip under continuous operation. Current levels below this

value never result in an overload trip. For example, a service
factor of 1.15 implies continuous operation up to 115% of
nameplate motor current.

Parameter number

9

File:group

Motor/Inverter:Motor Nameplate

Parameter type

destination

Display

x.xx

Factory default

1.15

Minimum value

1.00

Maximum value

2.00

Conversion

4096 = 1.00

10

PWM Frequency

Enter the drive carrier frequency in Hz. The drive carrier
frequency depends on your application and drive size. The drive
carrier frequency affects the audible noise level of your motor.

Parameter number

10

File:group

Motor/Inverter:Inverter

Parameter type

destination

Display

x Hz

Factory default

4000 Hz

Minimum value

1000 Hz

Maximum value

from the drive type

Conversion

1 = 1

11

Inverter Amps

Inverter Amps provides the current rating of the inverter. The
drive automatically sets Inverter Amps at power up.

Parameter number

11

File:group

Motor/Inverter:Inverter

Parameter type

source

Display

x.x amps

Factory default

not applicable

Minimum value

0.1 amps

Maximum value

from drive type

Conversion

10 = 1.0

12

Inverter Volts

Inverter Volts is the drive nameplate voltage rating of the inverter.
The drive automatically sets Inverter Volts at power up.

Parameter number

12

File:group

Motor/Inverter:Inverter

Parameter type

source

Display

x volts

Factory default

not applicable

Minimum value

75 volts

Maximum value

575 volts

Conversion

1 = 1

# of Motor Poles

Must be greater than 64

# of Motor Poles

Must be greater than 64