131 ramp/clflt owner, 132 flux/trim owner – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 241

Advertising
background image

Parameters

11-43

131

Ramp/ClFlt Owner

You can use the lower byte of Ramp/ClFlt Owner (bits 0 through
7) to see which SCANport device(s) are presently issuing a valid
Clear Fault command. You can use the higher byte (bits 8
through 15) to see which SCANport device(s) are presently
issuing a valid ramp command. You can choose between:

0 = Ramp/clear fault input not present
1 = Ramp/clear fault input present

The bits are defined as follows:

Parameter number

131

File:group

Monitor Status:SCANport Status

Interface/Comm:SCANport Status

Parameter type

source

Display

bits

Factory default

not applicable

Minimum value

00000000.00000000

Maximum value

11111111.11111111

Conversion

1 = 1

Refer to Chapter 8, Using the SCANport Capabilities, for more
information.

Bit

Description

0

ClrFlt L Opt
The L Option board owns the
Clear Fault.

1

ClrFlt SP 1
SCANport device 1 owns the
Clear Fault.

2

ClrFlt SP 2
SCANport device 2 owns the
Clear Fault.

3

ClrFlt SP 3
SCANport device 3 owns the
Clear Fault.

4

ClrFlt SP 4
SCANport device 4 owns the
Clear Fault.

Bit

Description

5

ClrFlt SP 5
SCANport device 5 owns the
Clear Fault.

6

ClrFlt SP 6
SCANport device 6 owns the
Clear Fault.

7

ClrFlt P197
Logic Cmd Input (parameter 197)
owns the Clear Fault.

8

Ramp L Opt
The L Option owns the Ramp.

9

Ramp SP 1
SCANport device 1 owns the
Ramp.

10

Ramp SP 2
SCANport device 2 owns the
Ramp.

Bit

Description

11

Ramp SP 3
SCANport device 3 owns the
Ramp.

12

Ramp SP 4
SCANport device 4 owns the
Ramp.

13

Ramp SP 5
SCANport device 5 owns the
Ramp.

14

Ramp SP 6
SCANport device 6 owns the
Ramp.

15

Ramp P197
Logic Cmd Input (parameter 197)
owns the Ramp.

132

Flux/Trim Owner

You can use the lower byte of Flux/Trim Owner (bits 0 through 7)
to see which SCANport device(s) are currently issuing a valid
process trim command. You can use the higher byte (bits 8
through 15) to see which SCANport device(s) are presently
issuing a valid flux command. You can choose between:

0 = Flux/trim input not present
1 = Flux/trim input present

The bits are defined as follows:

Parameter number

132

File:group

Monitor Status:SCANport Status

Interface/Comm:SCANport Status

Parameter type

source

Display

bits

Factory default

not applicable

Minimum value

00000000.00000000

Maximum value

11111111.11111111

Conversion

1 = 1

Refer to Chapter 8, Using the SCANport Capabilities, for more
information.

Bit

Description

0

Trim L Opt
The L Option board owns the
Trim.

1

Trim SP 1
SCANport device 1 owns the
Trim.

2

Trim SP 2
SCANport device 2 owns the
Trim.

3

Trim SP 3
SCANport device 3 owns the
Trim.

4

Trim SP 4
SCANport device 4 owns the
Trim.

5

Trim SP 5
SCANport device 5 owns the
Trim.

Bit

Description

6

Trim SP 6
SCANport device 6 owns the
Trim.

7

Trim P197
Logic Cmd Input (parameter 197)
owns the Trim.

8

Flux L Opt
The L Option owns the Flux.

9

Flux SP 1
SCANport device 1 owns the
Flux.

10

Flux SP 2
SCANport device 2 owns the
Flux.

Bit

Description

11

Flux SP 3
SCANport device 3 owns the
Flux.

12

Flux SP 4
SCANport device 4 owns the
Flux.

13

Flux SP 5
SCANport device 5 owns the
Flux.

14

Flux SP 6
SCANport device 6 owns the
Flux.

15

Flux P197
Logic Cmd Input (parameter 197)
owns the Flux.