11-10

Parameters

1

Language Select

Use Language Select to choose between a primary language
and an alternate language. Select:

• 0 to choose the primary language

• 1 to choose the alternate language

Parameter number

1

File:group

none

Parameter type

linkable destination

Display

x

Factory default

0

Minimum value

0

Maximum value

1

Conversion

1 = 1

2

Nameplate HP

Nameplate HP contains the value of the motor horsepower that
you entered during the start up routine. This value is typically
located on the motor nameplate.

Parameter number

2

File:group

Motor/Inverter:Motor Nameplate

Parameter type

destination

Display

x .x hp

Factory default

30.0 hp

Minimum value

0.2 hp

Maximum value

2000.0 hp

Conversion

10 = 1.0

3

Nameplate RPM

Nameplate RPM contains the value of the motor speed that you
entered during the start up routine. This value is typically located
on the motor nameplate. This value should not be the
synchronous speed of the motor.

Parameter number

3

File:group

Motor/Inverter:Motor Nameplate

Parameter type

destination

Display

x rpm

Factory default

1750 rpm

Minimum value

1 rpm

Maximum value

15000 rpm

Conversion

1 = 1

4

Nameplate Amps

Nameplate Amps contains the value of the current rating of the
motor that you entered during the start up routine. This value is
typically located on the motor nameplate. The drive uses this
information to properly tune to the motor.

Parameter number

4

File:group

Motor/Inverter:Motor Nameplate

Parameter type

destination

Display

x.x amps

Factory default

0.2 amps

Minimum value

0.1 amps

Maximum value

calculated

Conversion

10 = 1.0

5

Nameplate Volts

Nameplate Volts contains the voltage rating of the motor that you
entered during the start up routine. This value is typically located

on the motor nameplate.

Parameter number

5

File:group

Motor/Inverter:Motor Nameplate

Parameter type

destination

Display

x volt

Factory default

460 volts

Minimum value

75 volts

Maximum value

575 volts

Conversion

1 = 1

6

Nameplate Hz

Nameplate Hz contains the value of the frequency rating of the
motor that you entered during the start up routine. This value is
typically located on the motor nameplate.

Parameter number

6

File:group

Motor/Inverter:Motor Nameplate

Parameter type

destination

Display

x.x Hz

Factory default

60.0 Hz

Minimum value

1.0 Hz

Maximum value

250.0 Hz

Conversion

10 = 1.0