252

Step 2 Speed

Parameter 252 sets the rpm value for this step. (Scaling: 4096 =
Base Speed)

Parameter number

252

File:group

Profile Test Data

Parameter type

Setup

Display

+/- x.x rpm

Factory default

+0.0 rpm

Minimum value

-8 x base speed

Maximum value

+8 x base speed

Conversion

4096 = Base Motor Speed

253

Step 2 Value

Parameter 253 sets the time in seconds for time steps, the
counts in units for encoder steps, and the TB3 input to trigger on
for TB Input steps. Scaling:

Time Step: 10 x desired value (10 = 1.0 sec)
Encoder Step: 10 = 1.0 unit
TB Input Step: dependent on [L Option Mode Sel]. See P241.

Parameter number

253

File:group

Profile Test Data

Parameter type

Setup

Display

x.xS, x, x.x units

Factory default

0.0,0, 0.0

Minimum value

0.0,0, 0.0

Maximum value

3276.7, 5, 3276.7

Conversion

0=1.0 sec., x TBin, 10 = 1.0 unit

254

Step 2 Type

Parameter 251 selects the type of step to be used

0 = Not Used (This forces an End Action)
1 = Time Step, operate at speed shown in P252 for time in P253.
2 = TB3 Input Step, operate at speed shown in P252 until this
input goes true.
3 = Encoder Step, operate at speed shown in P252 for units in
P253.

Parameter number

254

File:group

Profile Test Data

Parameter type

Setup

Display

x

Factory default

0

Minimum value

0

Maximum value

3

Conversion

None

255

Step 3 Speed

Parameter 255 sets the rpm value for this step. (Scaling: 4096 =
Base Speed)

Parameter number

255

File:group

Profile Test Data

Parameter type

Setup

Display

+/- x.x rpm

Factory default

+0.0 rpm

Minimum value

-8 x base speed

Maximum value

+8 x base speed

Conversion

4096 = Base Motor Speed

256

Step 3 Value

Parameter 256 sets the time in seconds for time steps, the
counts in units for encoder steps, and the TB3 input to trigger on
for TB Input steps. Scaling:

Time Step: 10 x desired value (10 = 1.0 sec)
Encoder Step: 10 = 1.0 units
TB Input Step: dependent on [L Option Mode Sel]. See P241.

Parameter number

256

File:group

Profile Test Data

Parameter type

Setup

Display

x.xS, x, x.x units

Factory default

0.0,0, 0.0

Minimum value

0.0,0, 0.0

Maximum value

3276.7, 5, 3276.7

Conversion

0=1.0 sec., x TBin, 10 = 1 unit

257

Step 3 Type

Parameter 257 selects the type of step to be used

0 = Not Used (This forces an End Action)
1 = Time Step, operate at speed shown in P255 for time in P256.
2 = TB3 Input Step, operate at speed shown in P255 until this
input goes true.
3 = Encoder Step, operate at speed shown in P255 for units in
P256.

Parameter number

257

File:group

Profile Test Data

Parameter type

Setup

Display

x

Factory default

0

Minimum value

0

Maximum value

3

Conversion

None