127 clr flt/res mask, 128 dir/ref owner – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 239

Advertising
background image

Parameters

11-41

127

Clr Flt/Res Mask

You can use the lower byte of Clr Flt/Res Mask (bits 0 through 7)
to select which SCANport devices can issue a Reset Drive
command. You can use the higher byte (bits 8 through 15) to
select which SCANport devices can issue a Clear Faults
command. You can choose between:

0 = Disable control
1 = Enable control

The bits are defined as follows:

Parameter number

127

File:group

Interface/Comm:SCANport Config

Parameter type

linkable destination

Display

bits

Factory default

11111111.11111111

Minimum value

00000000.00000000

Maximum value

11111111.11111111

Conversion

1 = 1

Refer to Chapter 8, Using the SCANport Capabilities, for more
information.

Bit

Description

0

Reset L Opt
Let the L Option board control
resets.

1

Reset SP 1
Let SCANport device 1 control
resets.

2

Reset SP 2
Let SCANport device 2 control
resets.

3

Reset SP 3
Let SCANport device 3 control
resets.

4

Reset SP 4
Let SCANport device 4 control
resets.

5

Reset SP 5
Let SCANport device 5 control
resets.

Bit

Description

6

Reset SP 6
Let SCANport device 6 control
resets.

7

Reset P197
Let Logic Cmd Input
(parameter 197) control resets.

8

ClrFlt L Opt
Let the L Option board control
clear fault commands.

9

ClrFlt SP 1
Let SCANport device 1 control
clear fault commands.

10

ClrFlt SP 2
Let SCANport device 2 control
clear fault commands.

11

ClrFlt SP 3
Let SCANport device 3 control
clear fault commands.

Bit

Description

12

ClrFlt SP 4
Let SCANport device 4 control
clear fault commands.

13

ClrFlt SP 5
Let SCANport device 5 control
clear fault commands.

14

ClrFlt SP 6
Let SCANport device 6 control
clear fault commands.

15

ClrFlt P197
Let Logic Cmd Input
(parameter 197) control clear
fault commands.

128

Dir/Ref Owner

You can use the lower byte of Dir/Ref Owner (bits 0 through 7) to
see which SCANport device currently has exclusive control of the
reference changes. You can use the higher byte (bits 8 through
15) to see which SCANport device currently has exclusive control
of direction changes. You can choose between:

0 = Reference/direction input not present
1 = Reference/direction input present

The bits are defined as follows:

Parameter number

128

File:group

Monitor Status:SCANport Status

Interface/Comm:SCANport Status

Parameter type

source

Display

bits

Factory default

not applicable

Minimum value

00000000.00000000

Maximum value

11111111.11111111

Conversion

1 = 1

Refer to Chapter 8, Using the SCANport Capabilities, for more
information.

Bit

Description

0

Refer L Opt
The L Option board owns the
reference command.

1

Refer SP 1
SCANport device 1 owns the
reference command.

2

Refer SP 2
SCANport device 2 owns the
reference command.

3

Refer SP 3
SCANport device 3 owns the
reference command.

4

Refer SP 4
SCANport device 4 owns the
reference command.

5

Refer SP 5
SCANport device 5 owns the
reference command.

Bit

Description

6

Refer SP 6
SCANport device 6 owns the
reference command.

7

Refer P197
Logic Cmd Input (parameter 197)
owns the reference command.

8

Direct L Opt
The L Option board owns the
direct command.

9

Direct SP 1
SCANport device 1 owns the
direct command.

10

Direct SP 2
SCANport device 2 owns the
direct command.

Bit

Description

11

Direct SP 3
SCANport device 3 owns the
direct command.

12

Direct SP 4
SCANport device 4 owns the
direct command.

13

Direct SP 5
SCANport device 5 owns the
direct command.

14

Direct SP 6
SCANport device 6 owns the
direct command.

15

Direct P197
Logic Cmd Input (parameter 197)
owns the direct command.