Using the hysteresis function, Using the hysteresis function -23 – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 193

Advertising
background image

Using the Function Block

10-23

As an example the following table shows several drive unit values
converted to rpm. A base speed of 1755 is used for this table.

The formula for converting from rpm to internal units is as follows:

The following table shows several values in rpm converted to drive
units. Again, a base speed of 1755 is used.

Using the Hysteresis Function

The hysteresis function lets you select a value based on whether
Input 1 is greater than Input 4 or less than Input 5. If Input 1 is
between Input 4 and Input 5, then the value does not change.
Figure 10.27 shows the parameters that are used for the hysteresis
function and how these parameters are evaluated.

Speed Reference

RPM

Whole

Fraction

32767

65535

14039.99999346

4096

0

1755.00000000

1

0

0.42846680

0

65535

0.42846026

0

32767

0.21422686

0

1

0.00000654

-4

32711

-1.50000645

-4096

0

-1755.00000000

RPM

Speed Reference

Whole

Fraction

1755

4096

0

0.4284668

1

0

0.42846026

0

65535

0.9

2

6587

-1755

-4096

0

-1.5

-4

32711

2000

4667

52839

0.5

1

10941

y rpm

base motor speed

4096

65536

×

(

)

(

)

----------------------------------------------------------------------------------------

65536

----------------------------------------------------------------------------------------------

Whole, Fractional (remainder)

=

Advertising