176

Autotune Errors

Autotune Errors shows the results of the auto-tune tests. The test
results are divided into four categories: slip calculations, leakage
inductance tests, resistance tests, and flux current tests. If a fault
occurred during the auto-tune tests, the appropriate bit is set in
Autotune Errors. If no bits are set, the drive passed all of the
auto-tune tests.

The bits are defined as follows:

Parameter number

176

File:group

Autotune:Autotune Status

Parameter type

source

Display

bits

Factory default

not applicable

Minimum value

00000000.00000000

Maximum value

11111111.11111111

Conversion

1 = 1

Refer to Chapter 13, Understanding the Auto-tuning Procedure,
for more information.

Bit

Description

Bit

Description

Bit

Description

0

Slip <= 0

Resistance Tests

Flux Current Tests

Slip is 0 or negative.

6

Res- > 0 Spd

11

Flx-Atune Lo

Inductance Tests

Not at zero speed.

Auto-tune setpoint is too low.

1

Ind- > 0 Spd

7

Res-Sign Err

12

Flx-Flux < 0

Not at zero speed.

Sign error.

Flux less than zero.

2

Ind-Sign Err

8

Res- 0 Cur

13

Flx-Cur>MCur

Sign error or negative Lsigma.

Zero current.

Flux current > rated motor current.

3

Ind- 0 Cur

9

Res-SW Err

14

Flx-En Drop

Zero current.

Software error.

Enable dropout.

4

Ind-A/D Ovfl

10

Res-En Drop

15

Flx-Hi Load

A/D overflow at minimum gain.

Enable dropout.

The load is too high.

5

Ind-En Drop
Enable dropout.

177

Ki Freq Reg

Ki Freq Reg contains the integral gain of the frequency regulator
in encoderless mode. Do not change the value of this parameter.

Parameter number

177

File:group

none

Parameter type

destination

Display

x

Factory default

300

Minimum value

0

Maximum value

32767

Conversion

1 = 1

178

Kp Freq Reg

Kp Freq Reg contains the proportional gain of the frequency
regulator in encoderless mode. Do not change the value of this
parameter.

Parameter number

178

File:group

none

Parameter type

destination

Display

x

Factory default

800

Minimum value

0

Maximum value

32767

Conversion

1 = 1

179

Kf Freq Reg

Kf Freq Reg contains the feed-forward gain of the frequency
regulator in encoderless mode. Do not change the value of this
parameter.

Parameter number

179

File:group

none

Parameter type

destination

Display

x.x

Factory default

1.0

Minimum value

0.0

Maximum value

128.0

Conversion

256 = 1.0