B-14

Control Block Diagrams

Refer to Chapter 9, Applications, for additional information about the
feedback device type selections.

Important: Even though Fdbk Device Type lets you change the
feedback device type, you should use the start up procedure to change
your feedback device. The start up procedure automatically changes
several related parameters, and changing Fdbk Device Type manually
will not re-set these parameters.

Selecting Your Feedback Filter

You can use Fdbk Filter Sel (parameter 65) to select the type of
feedback filter. You can choose among the following filters:

Encoderless w/dead band. Limits operation of drive below a reference
value of 1Hz. Drive Speed and torque regulators are clamped at zero
when speed reference is less than 1 Hz.

4

If you want to use

this feedback device type:

Select this

value:

file:

Control

group:

Speed Feedback

To select

this type of filter:

Select this

value:

No filter

0

A light 35/49
radian feedback
filter

1

A heavy 20/40
radian feedback
filter

2

rad/sec

gain

0 db

rad/sec

gain

35

49

0 db

–6 db

rad/sec

gain

20

40

0 db

–12 db