Step 10 Speed

Parameter 276 sets the rpm value for this step. (Scaling: 4096 =
Base Speed)

Parameter number

276

File:group

Profile Test Data

Parameter type

Setup

Display

+/- x.x rpm

Factory default

0.00 rpm

Minimum value

-8 x base speed

Maximum value

+8 x base speed

Conversion

277

Step 10 Value

Parameter 277 sets the time in seconds for time steps, the
counts in units for encoder steps, and the TB3 input to trigger on
for TB Input steps. Scaling:

Time Step: 10 x desired value (10 = 1.0 sec)
Encoder Step: 10 = 1.0 units
TB Input Step: dependent on [L Option Mode Sel] See P241

Parameter number

277

File:group

Profile Test Data

Parameter type

Setup

Display

x.xS, x, x.x units

Factory default

0.0,0, 0.0

Minimum value

0.0,0, 0.0

Maximum value

3276.7, 5, 3276.7

Conversion

10=1.0 sec., x TBin, 10 = 1 unit

278

Step 10 Type

Parameter 278 selects the type of step to be used

0 = Not Used (This forces an End Action)
1 = Time Step, operate at speed shown in P276 for time in P277.
2 = TB3 Input Step, operate at speed shown in P276 until this
input goes true. See P241.
3 = Encoder Step, operate at speed shown in P276 for units in
P277.

Parameter number

278

File:group

Profile Test Data

Parameter type

Setup

Display

x

Factory default

0

Minimum value

0

Maximum value

3

Conversion

279

Step 11 Speed

Parameter 279 sets the rpm value for this step. (Scaling: 4096 =
Base Speed)

Parameter number

279

File:group

Profile Test Data

Parameter type

Setup

Display

+/- x.x rpm

Factory default

0.00 rpm

Minimum value

-8 x base speed

Maximum value

+8 x base speed

Conversion

4096 = base sp

280

Step 11 Value

Parameter 280 sets the time in seconds for time steps, the
counts in units for encoder steps, and the TB3 input to trigger on
for TB Input steps. Scaling:

Time Step: 10 x desired value (10 = 1.0 sec)
Encoder Step: 10 = 1.0 units
TB Input Step: dependent on [L Option Mode Sel]. See P241

Parameter number

280

File:group

Profile Test Data

Parameter type

Setup

Display

x.xS, x, x.x units

Factory default

0.0,0, 0.0

Minimum value

0.0,0, 0.0

Maximum value

3276.7, 5, 3276.7

Conversion

10=1.0 sec., x TBin, 10 = 1 unit

281

Step 11 Type

Parameter 281 selects the type of step to be used

0 = Not Used (This forces an End Action)
1 = Time Step, operate at speed shown in P279 for time in P280.
2 = TB3 Input Step, operate at speed shown in P279 until this
input goes true.
3 = Encoder Step, operate at speed shown in P279 for units in
P280.

Parameter number

281

File:group

Profile Test Data

Parameter type

Setup

Display

x

Factory default

0

Minimum value

0

Maximum value

3

Conversion