Using the SCANport Capabilities

8-5

All 2/3-wire start inputs must be low before a low to high
transition will start the drive.

Closing both Run Fwd and Rev will start the drive in the last
direction it was running.

Opening all Run Fwd/Rev inputs stops the drive. If any of the
Run Fwd/Rev inputs are closed, the drive continues to run. To
stop the drive when any Run Fwd/Rev input is opened requires
the stop input to be wire ORed with the Run Fwd or Run Rev.

Stop input stops the drive.

The drive will not start if the stop input is open, the enable input
is open, or the drive is faulted. Use Drive/Inv Status
(parameter 15) bit 0, Run Ready, to know when the drive is ready
to start.

When using a combination of 2- and 3-wire:

Each wiring type operates as above.

2-wire has priority over 3-wire, so opening or closing and
opening 2-wire Run Fwd/Rev input will stop the drive even if
started by a 3-wire start.

Stop input stops the drive.

Determining Function Ownership

To determine which device is issuing a specific command, use
parameters 128 through 132:

file:

Interface/Comm

group:

SCANport Status

To determine which device is

issuing this command:

Check the high (bits 8 – 15)/

low (bits 0 – 7) byte:

Of this

parameter:

Stop

Low

129

Direction control

High

128

Start

High

129

Jog1

High

130

Jog2

Low

130

Speed reference

Low

128

Flux enable

High

132

Trim enable

Low

132

Ramp

High

131

Clear fault

Low

131