11-28

Parameters

77

Current Rate Lim

Enter the largest allowable rate of change for the current
reference signal. This number is scaled in units of maximum per
unit current every two milliseconds.

Parameter number

77

File:group

Control:Control Limits

Parameter type

linkable destination

Display

x.x%

Factory default

20.0%

Minimum value

calculated

Maximum value

200.0%

Conversion

4096 = 100.0%

78

Fast Flux Level

Enter the percent of rated motor current to be used to flux up the
motor fast. The larger the value, the faster the motor reaches
rated flux. To enable the fast flux up feature, you must set bit 8 in
Bus/Brake Option (parameter 13).

Parameter number

78

File:group

Application:Fast Flux Up

Parameter type

destination

Display

x.x%

Factory default

200.0%

Minimum value

100.0%

Maximum value

calculated

Conversion

4096 = 100.0%

Refer to the Enabling Fast Flux Up section of Chapter 12,
Troubleshooting, f
or more information.

79

DC Brake Current

1

Enter the percent of motor current to be used for DC braking the
motor. To enable DC braking, you need to set bit 9 in Bus/Brake
Opts
(parameter 13).

1 DC Brake Current was added in Version 2.xx.

Parameter number

79

File:group

Application:DC Braking/Hold

Parameter type

linkable destination

Display

x.x%

Factory default

50.0%

Minimum value

0.0%

Maximum value

calculated

Conversion

4096 = 100.0% current

Refer to Chapter 9, Applications, for more information.

80

DC Brake Time

1

Enter the period of time that the DC braking current should be
applied after a stop has been commanded. To enable DC
braking, you need to set bit 9 in Bus/Brake Opts (parameter 13).

1 DC Brake Time was added in Version 2.xx.

Parameter number

80

File:group

Application:DC Braking/Hold

Parameter type

destination

Display

x.x seconds

Factory default

10.0 seconds

Minimum value

0.0 seconds

Maximum value

6553.5 seconds

Conversion

10=1.0 seconds

Refer to Chapter 9, Applications, for more information.

81

Motor Speed

Motor Speed contains a filtered version of speed feedback. The
value displayed in Motor Speed is passed through a low pass
filter having a 125 millisecond time constant.

Parameter number

81

File:group

Monitor:Motor Status

Parameter type

source

Display

±x.x rpm

Factory default

not applicable

Minimum value

-8 x base motor speed

Maximum value

+8 x base motor speed

Conversion

4096 = base motor speed

82

Command Spd Sts

Command Spd Sts is the high word portion of a 32-bit speed
reference quantity. It is the input term for the Speed PI Regulator.

Parameter number

82

File:group

Monitor:Drive/Inv Status

Parameter type

source

Display

±x.x rpm

Factory default

not applicable

Minimum value

-8 x base motor speed

Maximum value

+8 x base motor speed

Conversion

4096 = base motor speed