12-8

Troubleshooting

Table 12.A
Fault Descriptions

Fault Code

and Text

LED

Information

Fault

Type

Description

Suggested Action

01027
Autotune Diag

VP, Flashing

red

Soft

The drive encountered a problem
while running the auto-tune tests.

When this condition occurs, the
drive coasts to a stop regardless
of the selected stop type.

Check Autotune Errors (parameter 176). For additional
information about Autotune Errors, refer to Chapter 13,
Understanding the Auto-tuning Procedure
.

01051
MtrOvrld Pnd

VP, Flashing

red

Soft

A motor overload is pending. The
drive has reached 95% of the
level required for a motor
overload trip (see fault 01052).

Check for possible motor overheating.

If the motor temperature is excessive, reduce the
accel/decel times (parameters 42 – 45) or reduce the
load.

If the motor temperature is acceptable, increase the
value of Motor Overload % (parameter 26).

If you do not want this condition to be reported as a fault,
change bit 3 in Fault Select 2 (parameter 22) to 0.

01052
MtrOvrld Trp

VP, Flashing

red

Soft

Motor overload tripped. The drive
has reached the level of
accumulated motor current over
time as set by Motor Overload %
(parameter 26).

Check for possible motor overheating.

• If the motor temperature is excessive, reduce the

accel/decel times (parameters 42 – 45) or reduce the
load.

• If the motor temperature is acceptable, increase the

value of Motor Overload % (parameter 26).

If you do not want this condition to be reported as a fault,
change bit 4 in Fault Select 2 (parameter 22) to 0.

01053
Mtr Stall

VP, Flashing

red

Soft

The drive is in a limit condition for
a period of time in excess of the
value specified in Motor Stall
Time
(parameter 25) with the
motor at zero speed.

Check Torque Limit Sts (parameter 87) to see which limit
has occurred. Increase the appropriate limit parameter
or reduce the load.

If you do not want this condition to be reported as a fault,
change bit 5 in Fault Select 2 (parameter 22) to 0.

01083
MtrOvrld Pend

VP, Flashing

green

Warning

Motor overload pending. The
drive has reached 95% of the
level required for a motor
overload trip (see fault 01084).

Check for possible motor overheating.

If the motor temperature is excessive, reduce the
accel/decel times (parameters 42 – 45) or reduce the
load.

If the motor temperature is acceptable, increase the
value of Motor Overload % (parameter 26).

If you do not want this condition to be reported as a
warning, change bit 3 in Warning Select 2
(parameter 23) to 0.

01084
MtrOvrld Trp

VP, Flashing

green

Warning

Motor overload tripped. The drive
has reached the level of
accumulated motor current over
time as set by Motor Overload %
(parameter 26).

Check for possible motor overheating.

If the motor temperature is excessive, reduce the
accel/decel times (parameters 42 – 45) or reduce the
load.

If the motor temperature is acceptable, increase the
value of Motor Overload % (parameter 26).

If you do not want this condition to be reported as a
warning, change bit 4 in Warning Select 2
(parameter 23) to 0.

01085
Mtr Stall

VP, Flashing

green

Warning

The drive is in a limit condition for
a period of time in excess of the
value specified in Motor Stall
Time
(parameter 25) with the
motor at zero speed.

Check Torque Limit Sts (parameter 87) to see which limit
has occurred. Increase the appropriate limit parameter
or reduce the load.

If you do not want this condition to be reported as a
warning, change bit 5 in Warning Select 2
(parameter 23) to 0.