191

Relay Config 4

1

Use Relay Config 4 to select the function of terminals 7, 8, and 9
of either TB10 (for frames A1 – A4) or TB11 (for frames B – H)
output.

1 Relay Config 4 was added in Version 2.xx.

Relay Config 4 may be any one of the following values:

Parameter number

191

File:group

Interface/Comm:Digital Config

Parameter type

destination

Display

x

Factory default

32

Minimum value

0

Maximum value

36

Conversion

1 = 1

Value Description

Value Description

Value Description

0

Disabled

16

Not Zero Spd

29

Faulted

The relay is disabled.

The motor is not at zero speed.

A fault has occurred.

1

Run Ready

17

Flux Ready

30

Not Faulted

The drive is ready to run.

The motor is ready to be fluxed up.

A fault has not occurred.

2

Not Run Rdy

18

Not Flux Rdy

31

Warning

The drive is not ready to run.

The motor is not ready to be fluxed up.

A warning has occurred.

3

Running

19

Flux Up

32

Not Warning

Commanded speed is not zero.

The drive feels the motor is fluxed up.

A warning has not occurred.

4

Not Running

20

Not Flux Up

33

Enable

Commanded speed is zero.

The drive feels the motor is not fluxed up.

Power is being applied to the

5

Stopping

21

Jogging

motor.

The drive is stopping.

The motor is jogging.

34

Not Enable

6

Not Stopping

22

Not Jogging

Power is not being applied to the

The drive is not stopping.

The motor is not jogging.

motor.

7

Stopped

23

At Limit

35

Function Val

The drive is stopped.

The motor is at the limit shown in

True when the value of Function

8

Not Stopped

Torque Limit Sts (parameter 87)

Output 1 (par. 213) and/or the

The drive is not stopped.

24

Not At Lim

value of Function Output 2

9

Accelerating

The motor is not at the limit shown in

(par. 214) are zero.

The motor is accelerating.

Torque Limit Sts (parameter 87).

36

Not Function Val

10

Not Accel

25

>= Speed

True when the values of both

The motor is not accelerating.

The motor speed is greater than or equal

Function Output 1 (par. 213) and

11

Decelerating

to Relay Setpoint 4 (parameter 192).

Function Output 2 (par. 214)

The motor is decelerating.

26

< Speed

are zero.

12

Not Decel

The motor speed is less than Relay

37

Function T/F

The motor is not decelerating.

Setpoint 4 (parameter 192).

True when timer or logical state of

13

At Set Speed

27

>=Current

add/sub or mult/div is true based

The motor is at the requested

The motor current is greater than or equal

on the selected function block.

speed.

to Relay Setpoint 4 (parameter 192).

38

Function T/F

14

Not Set Sp

28

<Current

False when timer or logical state of

The motor is not at the requested

The motor current is less than

add/sub or mult/div is false based

speed.

Relay Setpoint 4 (parameter 192).

on the selected function block.

15

At Zero Spd

39

@ Profile Position

The motor is at zero speed.

192

Relay Setpoint 4

1

Relay Setpoint 4 lets you specify the setpoint threshold for either
speed or current. Relay Setpoint 4 is only active if Relay Config 4
(parameter 191) is set to a value of 25, 26, 27, or 28.

1 Relay Config 4 was added in Version 2.xx.

Parameter number

192

File:group

Interface/Comm:Digital Config

Parameter type

linkable destination

Display

±x.x%

Factory default

+0.0%

Minimum value

-800.0%

Maximum value

+800.0%

Conversion

4096 = 100.0%