12-4

Troubleshooting

Configuring Faults and Warnings Group 1

You can configure which of the following faults you want to trip the
drive by using Fault Select 1 (parameter 20) and Warning Select 1
(parameter 21). Fault Select 1 and Warning Select 1 both have the
following bit definitions:

Bits 6 and 7 are reserved.

For each condition that you want the drive to fault on, set the
corresponding bit in Fault Select 1. When the drive trips on a
condition that you set to fault the drive, how the drive reacts depends
on which condition occurred.

For bits 0 through 5:

The red CP light turns on.

The motor coasts to a stop.

For bits 8 through 14:

The red VP light turns on.

The motor stops according to how bits 1 – 3 in Logic Options
(parameter 17) are set.

file:

Fault Setup

group:

Fault Config

This bit:

With this text:

Is defined as:

0

RidethruTime

A bus ridethrough timeout occurred.

1

Prechrg Time

A precharge timeout occurred.

2

Bus Drop

A bus voltage drop of 150V below the bus tracker
voltage. This is covered in detail later in this chapter.

3

Bus Undervlt

A bus voltage drop to a level below the value set in Line
Undervolts
(parameter 27).

4

Bus Cycles>5

More than 5 ridethroughs occurred within a 20 second
period.

5

Open Circuit

The fast flux up current is less than 50% of
commanded.

8

mA Input

A loss of input connection after it was established.

9

SP 1 Timeout

A communication loss with SCANport device 1.

10

SP 2 Timeout

A communication loss with SCANport device 2.

11

SP 3 Timeout

A communication loss with SCANport device 3.

12

SP 4 Timeout

A communication loss with SCANport device 4.

13

SP 5 Timeout

A communication loss with SCANport device 5.

14

SP 6 Timeout

A communication loss with SCANport device 6.

15

SP Error

Too many errors have occurred in the communications.

If this bit is set:

Then this stop type is used:

1

Coast

2

Current limit

3

Ramp