91 iq, 92 test data 1, 93 test select 1 – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 229: 94 test data 2

Advertising
background image

Parameters

11-31

91

Iq %

Iq % shows the value of torque current reference that is present
at the output of the current rate limiter. 100% is equal to 1 per unit
(pu) rated motor torque.

Parameter number

91

File:group

none

Parameter type

source

Display

±x.x%

Factory default

not applicable

Minimum value

-800.0%

Maximum value

+800.0%

Conversion

4096 = 100.0%

92

Test Data 1

Use Test Data 1 to view a data value that corresponds to the
value selected in Test Select 1 (parameter 93). Test Data 1 is a
diagnostic tool used to view internal drive parameters.

Parameter number

92

File:group

Monitor:Testpoints

Fault Setup:Testpoints

Parameter type

source

Display

±x

Factory default

not applicable

Minimum value

-32768

Maximum value

+32767

Conversion

1 = 1

93

Test Select 1

Test Select 1 is a diagnostic tool that you can use to access
specific test points. The value you enter specifies which data
value should be displayed in Test Data 1 (parameter 92).

Parameter number

93

File:group

Monitor:Testpoints

Fault Setup:Testpoints

Parameter type

linkable destination

Display

x

Factory default

0

Minimum value

0

Maximum value

65535

Conversion

1 = 1

If you enter this value for Test Select 1

(parameter 93):

Then, the value in Test Data 1 (parameter 92) represents the:

12

Precharge status

86

Approximate fluxing time

94

Test Data 2

Use Test Data 2 to view a data value that corresponds to the
value selected in Test Select 2 (parameter 95). Test Data 2 is a
diagnostic tool used to view internal parameters.

Parameter number

94

File:group

Monitor:Testpoints

Fault Setup:Testpoints

Parameter type

source

Display

±x

Factory default

not applicable

Minimum value

-32768

Maximum value

+32767

Conversion

1 = 1