Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 40

Advertising
background image

2-22

Mounting and Wiring Your 1336 IMPACT Drive

The typical analog input connections for unidirectional operation are
shown as follows:

The typical analog input connections for bidirectional operation can
be shown as follows:

-10V DC (Power Supply)

COM (Power Supply Common)

+10V DC (Power Supply)

IN + (Analog In)

IN - (Analog In)

ADC

A

Connect to
either A or C
(only one)

B

C

D

E

Note: Connect to only one set of inputs

-- IN4+ and IN4-

-- IN3+ and IN3-
-- IN2+ and IN2-
-- IN1+ and IN1-

Reference Pot

2.5 k

Ω Minimum

To TE
(Signal Ground Terminal Block)

Shield

F

A1–A4

B–H

A

J4–3

TB10–3

B

J4–2

TB10–2

C

J4–1

TB10–1

D

J7–1

TB10–4

E

J7–2

TB10–5

F

J7–3

TB10–6

Frames

-10V DC (Power Supply)

COM (Power Supply Common)

+10V DC (Power Supply)

IN + (Analog In)

IN - (Analog In)

ADC

A

Forward

Reverse

B

C

D

E

Note: Connect to only one set of inputs

-- IN4+ and IN4-

-- IN3+ and IN3-
-- IN2+ and IN2-
-- IN1+ and IN1-

Reference Pot

2.5 k

Ω Minimum

To TE
(Signal Ground Terminal Block)

Reverse

Forward

R

Reverse

Relay

Shield

F

A1–A4

B–H

A

J4–3

TB10–3

B

J4–2

TB10–2

C

J4–1

TB10–1

D

J7–1

TB10–4

E

J7–2

TB10–5

F

J7–3

TB10–6

Frames

If you are wiring a remote pot to your system, you may want to refer
to Chapter 9, Applications, and Appendix
B, Control Block
Diagrams, for additional information.