Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 195

Advertising
background image

Using the Function Block

10-25

As an example, you could use the hysteresis function to fine tune the
speed regulator across a broad speed range and ensure that the drive
does not oscillate between the two configurations at any particular
speed. To ensure that the speed regulator is finely tuned at both the
low and the high speed in the range, the drive is tuned for each speed,
and the two values of Spd Desired BW (parameter 161) are noted. The
drive uses the low value when it is at low speed. It uses the high value
when it is at high speed. When it is between the high speed and low
speed, it uses the last specified value. This example is shown in
Figure 10.29.

Figure 10.29
Example of Hysteresis

To set up the function block for this application, you would need to
enter the values shown in Figure 10.30.

Figure 10.30
Hysteresis Function Block

Time

Start

Speed

High

Low

Stop

High value is used

200

Func 1 Eval Sel

0

198

Function In1

199

Func 1 Mask/Val

Hysteresis Function Block

203

Func 2 Eval Sel

0

201

Function In2

202

Func 2 Mask/Val

212

Function Sel

206

Func 3 Eval Sel

0

204

Function In3

205

Func 3 Mask/Val

207

Function In4

208

Function In5

Function
Output 1

If:

Then:

In1 > In4

In2 —> Out 1

In1 < In5

In3 —> Out 1

In5 < In1 < In4

No change

14

Enter: 0 This value is not used.

Enter: 0 This value is not used.

Enter: 0 This value is not used.

Enter: Value of bandwidth for low speed

Enter: Value of bandwidth for high speed

81

Motor Speed

Enter: Value for low speed

Enter: Value for high speed

161

Spd
Desired
BW

213

Advertising