Using an encoder with the loption board, Using an encoder with the l option board – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 93

Advertising
background image

Using the L Option

5-11

Using an Encoder with the
L Option Board

If you have an L7E, L8E, and L9E board, you need to complete the
following steps to use the encoder:

1. Ground the encoder the cable shield.

2. Set the encoder voltage jumper to match the encoder used

(J1/J2:5V/12V) on the L Option board.

3. Connect phase A, phase A NOT, phase B, and phase B NOT.

4. Connect the power to the encoder.

Requirements for the Contact
Closure Interface Board (L4)

Figure 5.4 shows the wiring diagram for the L4 Option board.

Figure 5.4
L4 Option Board Wiring Diagram

Circuits used with the L4 Option board must be able to operate with
low = true logic. Reed type input devices are recommended.

If your drive is a(n):

Ground the encoder to the following

location on the control board:

A1, A2, A3, or A4 frame

J7 pin 9, 6, or 3

B, C, D, E, F, G, or H frame

TB10 pin 20, 17, 12, 9, or 6

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

Typical

Not Used

Isolated
+5V

Isolated
Ground

0.1

µf

0.1

µf

0.1

µf

10.7k

470

470

IGND

10.7k

TB3

In this state:

External circuits must:

low

Be capable of a sinking current of approximately 10 mA to pull
the terminal voltage low to 3.0V DC or less.

high

Let the terminal voltage rise to a voltage of 4.0 – 5.0V DC

Advertising