46 droop percent, 47 s-curve per cent, 48 ptrim output – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 219: 49 ptrim reference, 50 ptrim feedback

Advertising
background image

Parameters

11-21

46

Droop Percent

Use Droop Percent to specify the percent of base speed that the
speed reference is reduced when at full load torque. You can use
this feature to cause motor speed to droop with an increase in
load.

Parameter number

46

File:group

Control:Speed Regulator

Parameter type

linkable destination

Display

x.x%

Factory default

0.0%

Minimum value

0.0%

Maximum value

25.5%

Conversion

10 = 1.0

47

S-Curve Percent

1

Use S-Curve Percent to create an adjustable S curve ramp.
S-Curve Percent controls the level of filtering that is applied to the
output of the acceleration and deceleration ramp.

1 S-Curve Percent was added in Version 2.xx.

Parameter number

47

File:group

Control:Accel/Decel

Parameter type

linkable destination

Display

x.x%

Factory default

0.0%

Minimum value

0.0%

Maximum value

100.0%

Conversion

10 = 1.0%

Refer to the Speed Reference Selection Overview in Appendix B,
Control Block Diagrams
, for more information.

If S-Curve Percent is

set to:

Then the S-Curve is:

0

Not used.

50%

Applied for half of the ramp time.

100%

Applied for the entire ramp.

48

PTrim Output

PTrim Output represents the scaled and limited output of the
process trim function. You can use PTrim Output as a parameter
source or to offset the speed or torque reference. To offset the
speed or torque reference, you need to select either bit 0 or bit 1
in PTrim Select (parameter 51).

Parameter number

48

File:group

Application:Process Trim

Parameter type

source

Display

±x.x%

Factory default

not applicable

Minimum value

-800.0%

Maximum value

+800.0%

Conversion

4096 = 100.0%

Refer to the Trim Control Overview section in Appendix B,
Control Block Diagrams
, for more information.

49

PTrim Reference

PTrim Reference is the reference input value for process trim.
PTrim Reference and PTrim Feedback (parameter 50) are
compared and used to update PTrim Output (parameter 48).

Parameter number

49

File:group

Application:Process Trim

Parameter type

linkable destination

Display

±x.x%

Factory default

+0.0%

Minimum value

-800.0%

Maximum value

+800.0%

Conversion

4096 = 100.0%

Refer to the Trim Control Overview section in Appendix B,
Control Block Diagrams
, for more information.

50

PTrim Feedback

PTrim Feedback is the feedback input value for process trim.
PTrim Feedback and PTrim Reference (parameter 49) are
compared and used to update PTrim Output (parameter 48).

Parameter number

50

File:group

Application:Process Trim

Parameter type

linkable destination

Display

±x.x%

Factory default

+0.0%

Minimum value

-800.0%

Maximum value

+800.0%

Conversion

4096 = 100.0%

Refer to the Trim Control Overview section in Appendix B,
Control Block Diagrams
, for more information.

Advertising