Using the Function Block

As an example of the scale function block, you could ensure that the
speed reference is kept to within a 10% range. To do this, you need to
enter the values shown in Figure 10.26.

Figure 10.26
Example of the Scale Function Block

Converting Between Drive Units and RPM

This section is provided to help you convert between drive units and
rpm. The formula for the conversion is:

200

Func 1 Eval Sel

0

198

Function In1

199

Func 1 Mask/Val

Enter: 10

Enter: 0 This value is not used.

Scale Function Block

203

Func 2 Eval Sel

0

201

Function In2

202

Func 2 Mask/Val

10

Enter: 0 This value is not used.

212

Function Sel

13

10

4096

213

Function Output 1

206

Func 3 Eval Sel

0

204

Function In3

205

Func 3 Mask/Val

5

Enter: 0 This value is not used.

0

207

Function In4

In4

214

Function Output 2

209

Function In6

210

Function In7

In6

In7

208

Function In5

In5

In1
10

In2

In4, In5

10

100, 0

In3

In6, In7

5

1, 0

Input
Range

Output
Range

Enter: 100

Enter: 1

Enter: 0

Enter: 0

Enter 0 for parameter 211 as
this parameter is not used.

Speed Ref 1

65536

×

Speed Ref 1 Frac

+

(

)

Base motor speed

4096

65536

Ч

(

)

(

)

Ч

y rpm

=