Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 403

Advertising
background image

CE Conformity

E-5

Filter Mounting, Continued

1 Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with

equivalent attenuation. Shielding/armor must be bonded to the metal bottom plate. See requirements 5 & 6 on page E-1.

2 Refer to the Filter Selection table on page E-2 for frame references and corresponding catalog numbers.

1336 IMPACT

(Through-the-Wall Mounting)

Frames D & E

1336 IMPACT

(Conventional Mounting)

Frames D & E

Conduit Box

To Motor

Access Panel and

Input Terminal Block

Lower Access Panel

Filter Mounting

Bracket

Filter Mounting

Bracket

Important: Drive and filter must be
mounted to a common back plane with
a positive electrical bond. Spacing is
determined by Conduit Box.

Three-Phase

Input

To Motor

Three-Phase

Input

Conduit Box

Nipple/Fitting

1

1

1

1

1

1

2

2

Advertising