213

Function Output 1

1

Use Function Output 1 to view the results of the function block.
Function Output 1 is either a word value or the upper byte of a
double word, depending on the value of Function Sel
(parameter 212).

1 Function Output 1 was added in Version 2.xx.

Parameter number

213

File:group

Application:Prog Function

Parameter type

source

Factory default

not applicable

Conversion

1 = 1

If Function Sel (parameter 212) is 0 – 8, then:
Display

bits

Minimum value

00000000.00000000

Maximum value

11111111.11111111

If Function Sel (parameter 212) is 9, 10, 12 or 13, then:
Display

±x

Minimum value

-32767

Maximum value

+32767

If Function Sel (parameter 212) is 11, then:
Display

x

Minimum value

0

Maximum value

65535

Refer to Chapter 10, Using the Function Block, for more
information.

214

Function Output2

1

Use Function Output 2 to view the results of the function block.
Function Output 2 is the lower byte of a double word Function Sel
(parameter 212) is 11, 12, or 13.

1 Function Output 2 was added in Version 2.xx.

Parameter number

214

File:group

Application:Prog Function

Parameter type

source

Display

x

Factory default

not applicable

Minimum value

0

Maximum value

65535

Conversion

1 = 1

Refer to Chapter 10, Using the Function Block, for more
information.

215

Min Speed Limit

1

Use Min Speed Limit to specify the minimum speed that you want
the motor to run at. Min Speed Limit overrides any speed
references to lower speeds.

1 Min Speed Limit was added in Version 2.xx.

Parameter number

215

File:group

Control:Control Limits

Parameter type

linkable destination

Display

x.x rpm

Factory default

0.0 rpm

Minimum value

0.0 rpm

Maximum value

base motor speed

Conversion

4096 = base motor speed

216

Fstart Select

1

Use Fstart Select to activate the flying start feature when
operating in Encoderless mode. This allows encoderless mode
the ability to reconnect into a rotating motor and resume
operation.

Note: Encoder mode will automatically reconnect and does not
use the Fstart Select parameter.

1 Fstart Select was added in Version 3.xx.

Parameter number

216

File:group

Application: Flying Start

Parameter type

linkable destination

Display

x

Factory default

0

Minimum value

0

Maximum value

2

Conversion

1 = 1

Refer to Chapter 9, Applications, for more information.

Display#

Display Text

Description

0

Disabled

Flying start disabled

1

Last Speed

Flying start enabled — Beginning search from last known speed

2

Speed Param

Flying start enabled — Beginning search from Fstart Speed (parameter 217)