Through-put time, B-38, B-38 control block diagrams – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 376

Advertising
background image

B-38

Control Block Diagrams

Through-Put Time

You can use the following block diagram and table to determine the
maximum amount of time that it will take a command to execute.

For example, the time that it takes a speed reference to be converted
to an output current can be determined as follows:

SCANport Reference

4 ms

Velocity/Torque Control

2 ms

Adaptive F.O.C. Control/Commutation

1 ms

Total Time

7 ms

The maximum amount of time would thus be 7 ms. (It may take fewer
than 7 ms, but will not take more than 7 ms.) Note also that it would
take the same amount of time if an analog speed reference were used.

Adaptive

F.O.C. Control/

Commutation

(1 ms)

Pulse Train

Inputs

(4 ms)

Analog

Inputs

(4 ms)

Process

Trim

(12.5 ms)

Encoder

Inputs

(2 ms)

SCANport

Reference

(4 ms)

SCANport

Command

(4 ms)

L Option

Card Relay

Inputs

(8 ms)

SCANport

Logic

Evaluation

(50 ms)

Fault

Handler

(100 ms)

Relay

Output

(12.5 ms)

Analog

Outputs

(4 ms)

Torque

Control

(2 ms)

Velocity

Control

Output

Current

Commands

Faults

Velocity Reference

Torque Reference

* Programmable

Function

Blocks

(12.5 ms)

* 12.5 ms through put time is in addition

to the other scan times of the I/Os.

Command

Parameter

Link

Scanner

(4 ms)

Execution Order Table

Interval

Functions

1 ms

Field Oriented Control

2 ms

Encoder Inputs
Velocity Regulator
Torque Reference

4 ms

SCANport Reference/Commands
Pulse Train Inputs
Analog Inputs
Analog Outputs
Parameter Link Scanner
Velocity Reference

8 ms

L Option Card Relay Inputs

12.5 ms

Programmable Function Blocks
Relay Outputs
Process Trim

50 ms

SCANport Logic Evaluation
Drive Logic Start/Stop Sequencing

100 ms

Fault Handler