10-2

Using the Function Block

Figure 10.1
Function Block Overview

Continued on Next Page

210

211

200

Func 1 Eval Sel

0 – 17

198

Function In1

199

Func 1 Mask/Val

I

V

Function Block

203

Func 2 Eval Sel

0 – 17

201

Function In2

202

Func 2 Mask/Val

I

V

212

Function Sel

In1

In2

206

Func 3 Eval Sel

0 – 17

204

Function In3

205

Func 3 Mask/Val

I

V

In3

207

Function In4

208

Function In5

In4

In5

213

Function
Output 1

209

Function In6

Function In7

In6

In7

Function In8

In8

Timer Delay

State Machine

In4

Off Time

In5

On Time

In1

In4

Off Time

In5

On Time

In4

Off Time

In5

On Time

0

In1 Or In2

1

In1 Nor In2

2

In1 And In2

3

In1 Nand In2

4

(In1 Or In2) And In3

5

(In1 And In2) Or In3

6

(In1 Timer Or In2) And In3

7

(In1 Timer And In2) Or In3

8

And In1

Then this

If In2 is: Timer is:

output is used:

False

False

In3

False

True

In6

True

False

In7

True

True

In8

Add/Subtract

9

In1 + In2 = Out1

Maximum/Minimum

10 In1, In2 > [max]Out1

In1, In2 < [min]Out1
In3:

If:

Then:

False min —> Out1
True

max —> Out1

Up/Down Counter

11

In1

Count up (rising edge)

In2

Count down (rising edge)

In3

Load counter with 0

In4

Up increment

In5

Down increment

In6

If:

Then:

False Word —> Out1
True

Double word —> Out1, Out2

Multiply/Divide

12 (In1 x In2)/In3 = Out1, Out2

In4

If:

Then:

False Per unit math is used.
True

Standard math is used.

Scale

13

In

Out

In1

In2

In4, In5 Out1, Out2

In3

In6, In7

214

Function
Output 2

If:

Then:

True

In6—>Out 1

False In7—>Out 1

Out1

Out2

False = Value of 0
True = Value other than 0

232

Function In9

In9

233

Function In10

In10