Setting Up the Input/Output

4. Compare the output of the digital-to-analog conversion (C) with

the internal drive units (B).

In Figure 7.3, the values were different, so we used Step 5.

5. Calculate the scale. For example, if the output of the digital to

analog conversion is

±1024 and the internal drive units are ±4096,

the scale value should be 4 (4 x 1024 = 4096).

6. Enter the offset and scale values into the appropriate parameters.

Figure 7.4 shows another example of an analog input. In this
example, you have an analog input range of

±10V and you want an

internal range of

±4096 (4096 = base motor speed).

Figure 7.4
Example of Offset and Scale for Analog Inputs

The offset is 0 because the analog input and the internal range are
both

± ranges. When the ±10V range is converted to internal units,

you get a range of

±2048. To get the internal range of ±4096, you can

use a scale factor of 2 (2 x 2048 = 4096).

The 1336 IMPACT drive provides analog input filter parameters for
you to use if the analog values are unstable. The filter parameters use
a low pass filter to create a more stable value. You will lose some of
the available bandwidth by using these parameters.

Determining the Offset and Scale Values for an Analog
Output

To determine the offset and scale values for an analog output, you
need to know the following:

the range that you want for the analog output (for example, -5V to
+5V or 0V to 10V)

the range that the drive is using for the internal units (for
example, -2048 to +2048 or 0 to 4096)

If the values are:

Then you:

Go to:

Identical

Do not need to scale the value

Step 6

Different

Need to scale the value

Step 5

Analog

Input

Offset

Scale

+10

–10

+10

–10

+2048

–2048

+4096

–4096

2

0

0

0

0

Analog to

Digital

Converter

±10 =

±2048

Drive Output

Range of the analog

input after the offset

is applied

Range of the analog

input in internal

drive units

±10V pot

Because you already have the
correct range (

± to ±), you do

not need an offset.

By multiplying

±2048 by 2,

you get the

±4096 range

you were looking for

.